Yaskawa MEMOCON GL120 User Manual

Page 185

Advertising
background image

4.4 Communications Modules

— 4-129 —

Item

Specification

MEMOBUS Port Specifications

Communications

Method

Half-duplex stop-start synchronization

Transmission Levels

Conform to RS-232C.

Protocol

MEMOBUS protocol or any other protocol

Baud Rate

19,200/9,600/7,200/4,800/3,600/2,400/2,000/1,800/1,200/60

0/300/150 bps

Communications

Mode

RTU mode or ASCII mode

Data Format

The following data format is used between the master and

slaves, between the master and modems, and between

modems and slaves:

1) Data bit length: 8 (RTU mode) or 7 (ASCII mode) bits

2) Parity check: Yes or No

3) Parity: Odd or even

4) Stop bits: 1 or 2

Transmission Distance 15 m (Can be extended to 4.5 km maximum by using

Yaskawa modem.)

Transmission

Error Detection

CRC-16 (RTU mode) or

LRC

(ASCII mode)

Connector

D-sub connector (9-pin, female)

4. Using MEMOBUS Modules (RS-232)

1) Number of Modules

Together with MEMOBUS Modules (RS-422) explained in 4.4.6 MEMOBUS Modules
(RS-422)
, two MEMOBUS Modules can be used.

2) Installation Location

MEMOBUS Modules (RS-232) can be mounted to any slot of the Mounting Base of any
Rack of the local channel. It will occupy one slot.

3) MEMOBUS Ports

a) Devices connectable to MEMOBUS ports are shown in the following table. Each of

these devices must be equipped with an RS-232C interface. In addition, depending
on the type of device, the MEMOBUS port settings will need to be altered. This set-
tings are altered using the DIP switch on the front of the Module. Refer to 4) DIP
Switch
later in this section.

4

Advertising
This manual is related to the following products: