System Components: Functions and Specifications

4.4.12 YENET 1600-D Module cont.

— 4-196 —

d) Each pin’s function is shown in the following table.

Table 4.80 Function of DIP Switch

Pin No.

Settings

Function

1

Set the baud rate of the

YENET 1600 D

di

Pin 2

Pin 1

Baud rate

2

YENET 1600-D according to

the table on the right

ON

ON

Not used

2

the table on the right.

ON

OFF

500 kbps

OFF

ON

250 kbps

OFF

OFF

125 kbps

3

ON

Sets Modules to automatic recovery mode. This will automatically

recover data when normal operation is restored after a

malfunction has occurred in the communications power supply or

in communications.

OFF

Sets Modules to manual recovery mode. This allows manual

recovery of data after normal operation is restored when a

malfunction has occurred in the communications power supply or

communications.

4

ON

OFF

Reserved for testing by the manufacturer. This pin must be set to

OFF.

Note

Always use MONITOR Mode when manual recovery mode is selected. If MONITOR Mode is
set to OFF and a communications error occurs, recovery will not be possible except by reset-
ting the Module.

e) Examples of setting the DIP switch are shown below:

Example 1
When the DIP switch is set as shown in the diagram on the right,
the YENET 1600-D Module is set as follows:

• Automatic recovery mode

• 500 kbps

Example 2
When the DIP switch is set as shown in the diagram on the right,
the YENET 1600-D Module is set as follows:

• Manual recovery mode

• 125 kbps

7) Rotary Switch

a) The rotary switch is used to set the node addresses of YENET 1600-D Modules.

b) There is one rotary switch. The rotary switch has positions from 0 to 9 (Hex).

4

A

EXAMPLE

"

1234

4

1

SW

ON

1234

4

1

SW

ON