TM.iQp.07 iQpump Controller Programming Manual

Function Code

The function code specifies commands. There are four function codes supported by the drive, as shown below.

Table 36 MEMOBUS / Modbus Function Codes

Data

Configure consecutive data by combining the storage register address (test code for a loopback address) and the data the register contains.
The data length changes depending on the command details.

Error Check

Errors are detected during communication using CRC-16. Perform calculations using the following method:

1. The factory setting for CRC-16 communication is typically zero, but when using the MEMOBUS / Modbus system, set the factory

setting to one (e.g., set all 16 bits to 1).

2. Calculate CRC-16 using MSB as slave address LSB, and LSB as the MSB of the final data.
3. Calculate CRC-16 for response messages from the slaves and compare them to the CRC-16 in the response messages.

Function Code

(Hexadecimal)

Function

Command Message

Response Message

Min. (Bytes)

Max. (Bytes)

Min.* (Bytes)

Max. (Bytes)

03H

Reading / Holding Register Contents

8

8

7

37

06H

Write In Single Holding Register

8

8

8

8

08H

Loopback Test

8

8

8

8

10H

Write In Several Holding Registers

11

41

8

8

* Minimum bytes for a normal Response Message (error response message is always 5 bytes).