YASKAWA TM.iQp.07 iQpump Controller Programming Manual

217

P6-04 Low Flow Level

Setting Range:

0.0 ~ 6000.0 (*n1)

Factory Default: 0.0

(*n1) Displayed units are determined by parameter P6-02.

P6-05 Low Flow Detection Delay Time When Already Running

Setting Range:

0 ~ 6000 sec

Factory Default: 10

Refer to parameter P6-05 in Appendix A for description details.

P6-06 Low Flow Detection Wait Time At Start

Setting Range:

0.00 ~ 3600.0 min

Factory Default: 0.00

Refer to parameter P6-06 in Appendix A for description details.

P6-07 Low Flow Select

P6-08 Low Flow Auto-Restart Time

Setting Range:

0.1 ~ 6000.0 min

Factory Default: 3.0 min

Refer to parameter P6-08in Appendix A for description details.

P6-09 Accumulation Level Fine

Setting Range:

0.0 ~ 999.0 gal

Factory Default: 0.00

Refer to parameter P6-09 in Appendix A for description details.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P6-04



843

Low Flow Level
Low Flow Level

If the drive is running, and the flow goes below this level for more
than the P6-05 time, a Low Flow fault or alarm will occur. A setting
of 0 disables the low flow detection. If P1-01 = 3, a LOWFL fault
will stop all drives running on the network.

0.0 ~

6000.0

(*n1)

0.0

Programming



Denotes that parameter can be changed when the drive is running.

(*n1) Displayed units are determined by parameter P6-02.

Setting

Description

0

No Display

1

Alarm Only

2

Fault

3

Auto-Restart (time set by P6-08)