YASKAWA TM.iQp.07 iQpump Controller Programming Manual

291

Monitor List

Table 124 Monitor List

Parameter No.

Addr.

Hex

Parameter Name Digital

Operator Display

Description

Monitor

U1-01

0040

Auto Set-point Reference
Auto: Set-point

Auto Set-point Reference (speed command) monitor when in auto mode, frequency reference
(speed command) setting location when in hand mode. Units changeable via P1-02.

U1-02

0041

Output Frequency
Output Freq

Output frequency monitor in Hz.

U1-03

0042

Output Current
Output Current

Output current monitor.

U1-06

0045

Output Voltage
Output Voltage

Displays drive output voltage.

U1-07

0046

DC Bus Voltage
DC Bus Voltage

Displays DC bus voltage.

U1-08

0047

Output Power
Output kWatts

Displays drive output power.

U1-10

0049

Input Terminal Status
Input Term Sts

Displays drive input terminal status.

U1-11

004A

Output Terminal Status
Output Term Sts

Output terminal ON / OFF check.

U1-12

004B

Drive Operation Status
Int Ctl Sts 1

U1-13

004C

Cumulative Operation Time
Elapsed Time

Displays total operating or power-on time of the drive.

U1-14

004D

Software Number
FLASH ID

Displays drive's software number.

U1-15

004E

Terminal A1 Input Voltage
Term A1 Leve

l

Displays the input voltage on Terminal A1, as a percentage of 10 Vdc.

0

1: FWD. run
(Terminal S1) is ON.
1: REV. run
(Terminal S2) is ON.
1: Multi-function input 1
(Terminal S3) is ON.
1: Multi-function input 2
(Terminal S4) is ON.
1: Multi-function input 3
(Terminal S5) is ON.
1: Multi-function input 4
(Terminal S6) is ON.
1: Multi-function input 5
(Terminal S7) is ON.

0 0 0 0 0 0 0

1: Multi-function Contact 1
output 1 (Terminal M1-M2) is
ON.
1:Multi-function Contact 2
output 1 (Terminal M3-M4) is
ON.
Not used

Not used
1:Fault output
(Terminal MA/MB-MC) is
ON.

0 0 0 0 0 0 0 0

1: During running
1: During zero speed
1: During reverse
1: During reset signal input
1: During speed agree
1: Drive operation ready
1: During fault detection
(Minor fault)
1: During fault detection
(Major fault)

0 0 0 0 0 0 0 0