C2 S-Curve Acc

S-Curve Characteristics

Setting Range:

0.00 ~ 2.50 s

Factory Default: 0.20 s

Parameters C2-01 and C2-02 will affect the acceleration rate of the output frequency in order to reduce shock to the load. The S-curve
addition to the acceleration profile can ramp the acceleration rate from a 0 to the rate specified by the active Acceleration Time (C1-01 or
C1-03) and back to 0.

Figure 1.32

Figure 32. S-curve Characteristic Timing Diagram

The S-Curve transition into and out of the active acceleration rate can be programmed independently. C2-01 will ramp up the acceleration
from no acceleration up to the rate of C1-01 or C1-03. C2-02 will ramp the acceleration rate from the rate of C1-01 or C1-03 back down
to no acceleration (constant speed). The use of S-Curve characteristics will lengthen the overall acceleration time as follows:

Figure 1.33

Figure 33. S-Curve Characteristic Timing Diagram