TM.iQp.07 iQpump Controller Programming Manual

• PI is enabled (b5-01 > 0)
• Dual Zone PI is enabled (b5-01 = 2, P1-01 = 0, b5-09 = 0, and H3-09 = B)
• PI is NOT disabled via Multi-Function Digital Input
• Signal on Terminal A1 goes below -6.25% or above 106.25% for more than 1 s.

Note: Wire break detection on Terminal A1 occurs

after

the gain / bias parameters (h3-02 and H3-03) are applied.

Feedback Loss (wire-break):

The drive will then react depending on how parameter b5-12 is programmed. However, if b5-12 is set to “fault” (b5-12 = 2), the drive will
only fault when running in “Auto” mode. A warning will only be displayed if the drive is not running, or is running in “Hand” mode.

Feedback Loss (standard):

The drive will then react depending on how parameter b5-12 is programmed. However, if b5-12 is set to “fault” (b5-12 = 2), the drive will
only fault when running in “Auto” mode. A warning will only be displayed if the drive is running in “Hand” mode.

Note: To convert terminal A1 to a 4 ~ 20 mA signal, connect a 250 Ohm precision resistor (1/4 W or greater) between A1 and

AC. Then program H3-02 = 231.2% and H3-03 = 25.0%.

Table 11 Related Parameters

Table 12 Related Fault

Table 13 Multi-Function Output Setting

b5-13 PI Feedback Loss Detection Level

Setting Range:

0 ~ 100%

Factory Default: 0%

Refer to parameter b5-13 in appendix A for description details.

b5-14 PI Feedback Loss Detection Time

Setting Range:

0.0 ~ 25.0 s

Factory Default: 2.0 s

The iQpump drive interprets feedback loss whenever the feedback signal drops below the value of b5-13 and stays below that level for at
least the time set into b5-14. See

Figure 1.30

for timing details.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

b5-12

1B0

PI Feedback Reference Missing
Detection Selection
Fb los Det Sel

0: Disabled
1: Alarm
2: Fault

0 ~ 2

2

Programming

b5-13

1B1

PI Feedback Loss Detection
Level
Fb los Det Lvl

Sets the PI feedback lost detection level as a percentage of maximum
frequency (E1-04).

0 ~ 100%

0%

Programming

b5-14

1B2

PI Feedback Loss Detection
Time
Fb los Det Time

Sets the PI feedback loss detection delay time in terms of seconds.

0.0 ~

25.5 s

2.0 s

Programming

Fault Display

Description

Cause

Countermeasure

FBL Feedback

Loss

PI Feedback Loss PI Feedback source is not installed correctly or is not working.

Check to insure the PI Feedback source is installed and working
properly.

Setting

Description

4A

Transducer Loss
Closed: During a “Feedback Loss Alarm”
Closed: During a “FBL - Feedback Loss Fault”