P2-05 feedback detection drop time, P2-06 sleep mode: cycling protection – Yaskawa iQpump Controller Programming Manual User Manual

Page 162

Advertising
background image

162

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.116

Figure 120. No-Flow Detection During Deceleration

P2-05 Feedback Detection Drop Time

Setting Range:

0 ~ 3600 s

Factory Default: 10 s

The iQpump drive can be configured to detect a no-flow condition. The drive can be programmed to monitor the feedback signal during a
flow, no-flow condition for a programmed Feedback Detection Drop Time (P2-05).

The Feedback Detection Drop Time (P2-05) works in conjunction with the Delta Sleep Feedback Drop Level (P2-04).

P2-06 Sleep Mode: Cycling Protection

Setting Range:

0 ~ 10

Factory Default: 0

The iQpump drive can be configured to allow a maximum number of cycles before initiating a “Pump Over Cycle Fault (POC).” The
drive will determine the maximum number of cycles based on the programmed number in the Sleep Mode: Cycling Protection (P2-06).
One cycle is defined by the drive transferring from normal operation to sleep mode when operating in the Auto Mode. A value of 0
programmed into the Sleep Mode: Cycling Protection (P2-06) will disable this function.

The maximum time allowed between cycles can be programmed in the Sleep Mode: Maximum Cycling Protection Time (P2-07).

TIME

Output Frequency

Sleep Delay Time

P2-03

Feedback

Auto Mode Run

Sleep Active

Wait for Start

Sleep Level

P2-02

STOP, 0Hz

0%

OFF Mode

Start Level

P1-04

FB Drop

Check

AUTO MODE RUN

Ramp

Down

Start System, Incoming Run Command

Start System

Min. Frequency

P1-06

AUTO MODE RUN

Start Level Delay

P1-05

START DELAY

System

Set-Point

P2-04 Delta FB Drop Level

P2-05 Feedback Drop Detection Time

Sleep Detected

Feedback Drop

Detected