Yaskawa iQpump Controller Programming Manual User Manual
Page 225

YASKAWA TM.iQp.07 iQpump Controller Programming Manual
225
◆
P7-06 De-Scale Forward Run Time
Setting Range:
1 ~ 6000 s
Factory Default: 10 s
Refer to parameter P7-06 in Appendix A for description details.
◆
P7-07 De-Scale Reverse Run Time
Setting Range:
1 ~ 6000 s
Factory Default: 10 s
Refer to parameter P7-07 in Appendix A for description details.
◆
P7-08 De-Scale Acceleration Time
Setting Range:
0.0 ~ 600.0 s
Factory Default: 2.0 s
Refer to parameter P7-08 in Appendix A for description details.
◆
P7-09 De-Scale Deceleration Time
Setting Range:
0.0 ~ 600.0 s
Factory Default: 2.0 s
Refer to parameter P7-09 in Appendix A for description details.
◆
P7-10 De-Scale Pump Run Time
Setting Range:
1.0 ~ 2000.0 hrs
Factory Default: 168.0 hrs
Refer to parameter P7-10 in Appendix A for description details.
◆
P7-11 Anti-Jam Release Time
Setting Range:
0.5 ~ 10.0 s
Factory Default: 2.0 s
Refer to parameter P7-11 in Appendix A for description details.