P5-02 hand reference – Yaskawa iQpump Controller Programming Manual User Manual

Page 209

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

209

Hand Mode Operation from External Signal (P5-01 = 0)

Connection Diagram of Potentiometer

Figure 1.159

Figure 163.

Connection Diagram of External Signal

Figure 1.160

Figure 164.

P5-02 Hand Reference

Setting Range:

0.00 ~ 120.00 Hz

Factory Default: 40.00 Hz

The iQpump drive can be operated manually or in the “Hand” mode. The frequency reference for the hand mode is programmed in the
Hand Reference (P5-02).

The Hand Reference (P5-02) is used when the hand mode is active and the Hand Mode Reference Source (P5-01) is set to 1.

Refer to Hand Mode Reference Source (P5-01) for more details.

The Hand Reference (P5-02) works in conjunction with the Hand Mode Reference Source (P5-01). Allow the “Hand Mode” reference to
operate the same as a digital preset reference (d1-0x) so that it can be set from the “U1-01” menu. Although P5-02 will act as a normal
“d1-xx” frequency reference, it will not be affected by P1-02 / P1-03. The Operator MOP feature will NOT work with the Hand
Reference parameter.

If the thrust bearing function is enabled, P4-05 determines the minimum Hand Reference allowed.

Function Description:

<0034>

Internally forces a ‘simulated” frequency reference select MFDI that will then use the P5-02 as the reference.