YASKAWA TM.iQp.07 iQpump Controller Programming Manual

205

P4-21 Low City Pressure Input Select

<0034>

The Low City Pressure Input Select parameter prohibits the drive from running when low incoming pressure is indicated by a pressure
switch.

If the pressure switch is active (sufficient pressure available), the drive will operate normally. If the pressure switch indicates that
incoming pressure is to low:

• The lead drive will be forced into a sleep-like state (coast to stop).
• Any drives staged in multiplex mode will immediately be De-Staged (coast to stop).
• The alarm “Low City Pressure” will be displayed on the lead drive.
• The drive will restart but NOT perform a Pre-charge when sufficient pressure returns.
• The drive will start but WILL perform a Pre-charge if the Auto-Run command was given during the Low Pressure condition.

Figure 1.155

Figure 159. Low City Pressure Digital Input, Normally Closed (P4-21 = 1)

Table 81 Parameters

Table 82 Multi-Function Output Setting

<0034>

Table 83 Alarms

<0034>

Setting

Description

0

Normally Open (closed indicates the “Low City Pressure” condition)

1

Normally Closed (open indicates the “Low City Pressure” condition)

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P4-21



834

Low City Pressure Input Select
Low City In Sel

Selects the type of pressure switch connected to the “Low City Press”
digital input (H1-0x = 73).
0: Normally Open (closed indicates the “Low City Pressure”
condition).
1: Normally Closed (open indicates the “Low City Pressure”
condition).

0 ~ 1

1

Programming

P4-22



8356

Low City Pressure Input Delay
Low City Delay

Sets the amount of time a “Low City Pressure” condition needs to be
present before the drives will stop. Also sets the amount of time that
the pressure needs to be adequate before the drive system will re-
start.

1 ~ 1000 s

10

Programming



Denotes that parameter can be changed when the drive is running.

Setting

Description

73

Low City Press
Indicates that sufficient / insufficient pressure is present on the inlet to the pump. Used mainly for pressure booster stations.

Alarm Display

Description

Low City Pressure

Insufficient pressure is present on the inlet to the pump. Used mainly for pressure booster stations. Uses the “Low City Pressure”
digital input (H1-0x = 73) and parameters P4-21 and P4-22.

Low City Pressure

(H1-01 = 73)

P4-22

Low City Delay

Low City Pressure

Message

P4-22

Low City Delay

P4-22

Low City Delay

P4-22

Low City Delay

Output

Frequency

Thrust Bearing