72

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

To reset the Low Water Level Fault would require the removal of the run command, initiate a fault reset, and restart the drive using the
Pre-charge function.

IMPORTANT:

<0034>

Program P1-15 to 0 or 2 when the “Low Water” function is not used.

Note: Low Water Level Fault is only active in the Auto Mode and inactive during the Pre-charge function.

Figure 1.55

Figure 55. Lower Water Fault on Operator

Figure 1.56

Figure 56. Wiring Diagram

Function: Fixed Speed Auto (Setting: 86)

A digital input can be configured to enable the Fixed Speed Auto (H1-0x = 86) when operating in the Auto Mode. A contact closure into
the multi-function input will enable the Fixed Speed Auto function.

The Fixed Speed Auto will cause the drive to run at the iQpump drive Multi / Maximum Level (P3-02) and disable the PI Control, Sleep
Mode and Lead / Lag operation.

When the digital input is open, the Fixed Speed Auto is disabled.

Note: Pre-charge and Thrust Bearing functions have a higher priority than Fixed Speed Auto.

-DRIVE-

Low FB / Water

LFB /

U2-04 =
U2-05 =

0.00 Hz
0.00 A

External Switch or
Relay Contact

Low Water Level

H1-04 = 85
(Low Water Level)

S1

S2

S3 (H1-01)

S4 (H1-02)

S5 (H1-03)

S6 (H1-04)

S7 (H1-05)

SC

SP 24 VDC +/- 20%, 8 mA

E (G)

SN