P8 Pressure and Level Control

<0034>

For Quick Set-up procedures refer to TM.iQp.06 iQpump Drive User Manual, Appendix G.

P8-01 Pressure and Level Control Select

Setting Range:

0 ~ 1

Factory Default: 0

Controls the Constant Pressure With Well Draw Down Control.
0: Disabled
1: Enabled

Overview

This parameter will allow the drive to control pressure when there is adequate water inside of the well. When the well level drops to the
Water Level Setpoint (P8-03), it will regulate the well level and the pressure will be allowed to drop. The drive will also go to sleep, wake
up, and / or alarm / fault based on well water level.

Figure 1.170

Figure 174. System Overview

A2 - PI Fdbk.

A1 - Well Depth Fdbk.

Analog 4-20 mA

Pressure Sensor

Analog 4-20 mA

Liquid

Output

T1 T2 T3

P8-05 Wake-Up Level

P8-03 Water Level Setpoint

P8-04 Minimum Water level

P8-07 Water Alarm/Fault Level

Pump

Well Depth Sensor