YASKAWA TM.iQp.07 iQpump Controller Programming Manual

13

Figure 1.1

Figure 1. 2 and 3-Wire Control Wiring Examples

Important: Some parameters are unaffected by either the 2-Wire or 3-Wire initialization. The following parameters will not be reset
when parameter A1-03 = 2220 or 3330:

A1-04 Password Entry

Setting Range:

0 ~ 9999

Factory Default: 0

If parameters A1-01 through A1-03 are locked (unchangeable), they can be unlocked by entering the correct password number into
A1-04.

Once the correct password number is entered and the specified parameters are unlocked, a 2-Wire or 3-Wire initialization will reset the
password to 0000.

Note: A1-04 will return to “0000” when the password has been entered.

A1-05 Select Password

Setting Range:

0 ~ 9999

Factory Default: 0

When the value set into A1-04 does NOT match the value set into A1-05, parameters A1-01 thru A1-03 cannot be changed. All other
parameters determined by A1-01 can be changed. Parameter A1-05 can be accessed by displaying parameter A1-04, then press and hold
the RESET key along with the MENU key simultaneously.

A1-00

Language Selection

E1-03

V/f Pattern Selection

o2-04

kVA Selection

Note: 2-Wire Control is the most commonly used.

Stop switch
(NC contact)

Operation switch
(NO contact)

3-wire control

2-wire control

Run command
(run on momentary close)
Stop command
(stop on momentary close)

Sequence input common

S1

SN

S2

S1

SN

FWD Run/Stop