P6-10 accumulation level course, P6-11 accumulation behavior, P6-12 high flow level – Yaskawa iQpump Controller Programming Manual User Manual

Page 218: P6-13 high flow detection delay time

Advertising
background image

218

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

P6-10 Accumulation Level Course

Setting Range:

0 ~ 61036 kgl

Factory Default: 0

Refer to parameter P6-10 in Appendix A for description details.

P6-11 Accumulation Behavior

P6-12 High Flow Level

Setting Range:

0.0 ~ 6000.0 (*n1)

Factory Default: 0.0

(*n1) Displayed units are determined by parameter P6-02).

P6-13 High Flow Detection Delay Time

Setting Range:

1 ~ 6000 s

Factory Default: 10

Refer to parameter P6-13 in Appendix A for description details.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P6-09



848

Accumulation Level Fine
Accum Lvl Fine

Sets the accumulated volume that will trigger the Accum Level
alarm, Accum Level fault, or Accum Level digital output. Total
Accum Level can be calculated as follows: Total Accum Level =
P6-10 x 1000 + P6-09. If P1-01 = 3, an ACCUM fault will stop all
drives running on the network.

0.0 ~ 999.0

gal

0.0

Programming



Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P6-10



849

Accumulation Level Course
Accum Lvl Course

Sets the accumulated volume that will trigger the Accum Level
alarm, Accum Level fault, or Accum Level digital output. Total
Accum Level can be calculated as follows: Total Accum Level = P6-
10 x 1000 + P6-09. If P1-01 = 3, an ACCUM fault will stop all drives
running on the network.

0 ~ 61036

kgl

0

Programming



Denotes that parameter can be changed when the drive is running.

Setting

Description

0

No Display

1

Alarm Only

2

Fault

3

Auto-Restart (time set by P6-08)

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P6-12



48B

High Flow Level
High Flow Level

If the drive is running, and the flow goes above this level for more
than the P6-13 time, a High Flow fault or alarm will occur. A setting
of 0 disables the high flow detection. If P1-01 = 3, a HIFLO fault will
stop all drives running on the network.

0.0 ~

6000.0

(*n1)

0.0

Programming



Denotes that parameter can be changed when the drive is running.

(*n1) Displayed units are determined by parameter P6-02.