B1-03 stopping method, 00hz – Yaskawa iQpump Controller Programming Manual User Manual

Page 21

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

21

Table 1 Related Parameters

<0034>

Table 2 Digital Operator Display

Table 3 Fault

<0034>

Table 4 Message

<0034>

Table 5 Multi-Function Output Setting

<0034>

b1-03 Stopping Method

There are four methods of stopping the iQpump drive when the Run command is removed.

Parameter

No.

Addr. Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

P4-18



831

Run / Stop Control Run Time
R-S Run Time

This parameter sets the amount of time the drive will run for when
the Run / Stop Control is enabled. It will also set the “timed” run time
when enabled (b1-02 = 5).

0.0 ~

6000.0 min

0.0 min Programming

P4-19



832

Run / Stop Control Stop Time
R-S Stop Time

This parameter sets the amount of time the drive will stop for when
the Run / Stop Control is enabled.

0.0 ~

6000.0 min

0.0 min Programming

P4-20



833

Run / Stop Control Cycles
R-S Cycle Count

This parameter determines how many Run / Stop Cycles the drive
will execute before staying stopped.

0 ~ 1000

0

Programming

 Denotes that parameter can be changed when the drive is running.

Description

Operator Display

When the Run / Stop function is enabled, the display will change as shown.
The Run / Stop function is enabled by setting parameters P4-18, P4-19 and P4-20
to values greater than zero.

Fault Display

Description

Cause

Countermeasures

oPE15

Run / Stp-

Run / Stop or Timed Run enabled in
multiplex mode.

Run / Stop Control has been enabled when in multiplex mode.
(P1-01 > 0, P4-18 > 0, P4-19 > 0 and P4-20 > 0).
OR
Timed Run Control has been enabled when in multiplex mode.
(P1-01 > 0 and b1-02 = 5).

Reprogram P1-01, P4-18 ~ P4-20,
or b1-02.

Fault Display

Description

Cause

Countermeasures

Run / Stop Finished Run / Stop Cycles have completed.

The number of Run / Stop Cycles since the last HAND command
has completed.

Press “Off” to clear the message.

Setting

Description

51

Run / Stop - Stop
Closed: Drive is stopped due to the Run / Stop control (P4-18 and P4-19) OR
Closed: Drive is stopped because the Run / Stop cycles have completed (P4-20).

52

Run / Stop - Finish
Closed: Drive is stopped because the Run / Stop cycles have completed (P4-20).

Setting

Description

0

Ramp to Stop (

factory default

)

1

Coast to Stop

2

DC Injection to Stop

3

Coast w / Timer

Run/Stop Control

40.00Hz

0.00 Hz

0.0 PSI