P4-12 pre-charge frequency 2, P4-13 pre-charge time 2, P4-14 two motor alternation selection – Yaskawa iQpump Controller Programming Manual User Manual

Page 201

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

201

Table 76 Alarms

<0034>

Table 77 Multi-Function Output Setting

<0034>

P4-12 Pre-charge Frequency 2

<0034>

Setting Range:

0 ~ 120.00 Hz

Factory Default: 0.00 Hz

Refer to parameter P4-12 in Appendix A for description details.

P4-13 Pre-charge Time 2

<0034>

Setting Range:

0 ~ 3600.0 min

Factory Default: 0.0 min

Refer to parameter P4-13 in Appendix A for description details.

P4-14 Two Motor Alternation Selection

<0034>

This parameter allows one drive to power two motors in an “OR” configuration to keep the amount of wear on each motor / pump
balanced. This feature will utilize one digital output, which will drive two output contactors via a form-C pilot relay. This feature is only
available in Simplex mode (P1-01 = 0).

Alarm Display

Description

Cause

Countermeasures

Utility Delay Adjust by

P4-11

Utility Delay

This message will appear when the drive is delaying
the run command due to the Utility Start Delay
Function.

Wait until the P4-11 time to elapse, or cycle the run
command.

Setting

Description

50

Utility Delay
Closed: Drive is stopped and is waiting for the utility delay timer to expire. (configured by P4-11)

Setting

Description

0

Disabled

1

Enabled

2

Motor 1 Only

3

Motor 2 Only