YASKAWA TM.iQp.07 iQpump Controller Programming Manual

177

Figure 1.129

Figure 133.

Auxiliary Pump De-Staging (OFF)

The de-staging of the auxiliary pumps 2 and 3 will occur in the reverse order of the staging process described previously.

The de-staging of auxiliary pump 3 occurs when the output frequency falls below the Pump 3 Frequency Shutdown Level (P3-10) and the
difference between the system’s feedback minus the setpoint exceeds the value programmed in the Shutdown Pump Delta Level (P3-05)
for the time programmed in the Add Pump Delay Time (P3-04).

The de-staging of auxiliary pump 2 occurs when the auxiliary pump 3 is de-staged and the output frequency falls below the Pump 2
Frequency Shutdown Level (P3-09) and the difference between the system’s feedback level minus the setpoint exceeds the value
programmed in the Shutdown Pump Delta Level (P3-05) for the time programmed in Shutdown Pump Delay Time (P3-06). Refer to

Figure 134.

for the de-staging of the auxiliary pumps using the “output frequency + feedback level” control method.

System

Set-Point

Start Level

P1-04

0%

Auto Mode Run

OFF Mode

Multi-function

Output #41

Wait for Start

Start System

Start System, Incoming Run Command

TIME

Multi-function

Output #40

START DELAY

AUTO MODE RUN: PUMP 1

RUN

Feedback

ADD PUMP 2

Close Contact

ADD PUMP 3

Close Contact

Start Level Delay

P1-05

Add Pump Delay Time

P3-04

Multiplex Stablize Time

P3-11

Add Pump Delay Time

P3-04

Multiplex Stablize Time

P3-11

Add Pump Delta Level P3-03

Multi/Maximum

Level P3-02

Output Frequency