YASKAWA TM.iQp.07 iQpump Controller Programming Manual

151

Figure 1.110

Figure 114. Not Maintaining Setpoint (NMS) Fault

Table 55 Messages

<0034>

P1-12 Not Maintaining Setpoint Time

<0034>

Setting Range:

0 ~ 3600 s

Factory Default: 60 s

The iQpump drive can be configured to display a Not Maintaining Setpoint (P1-12) fault when the difference between the setpoint and
the feedback levels are exceeded for the time programmed in the Not Maintaining Setpoint (P1-12). The drive will coast to a stop after the
level has been exceeded for the specified time programmed in P1-12.

This function is only active during operation in the Auto Mode.

The Not Maintaining Setpoint Time (P1-12) is also used for the Prime Loss Level (P1-14) function. Refer to Prime Loss Level (P1-14)
for more details.

The Not Maintaining Setpoint Time (P1-12) works in conjunction with Maximum Setpoint Difference (P1-11) and Prime Loss Level (P1-
14).

Note: The time value programmed into P1-12 is shared by Maximum Setpoint Difference (P1-11) and Prime Loss Level

(P1-14) functions. However, independent times are maintained. If one function time; such as P1-11, has elapsed, the
other functions time (P1-14) is still maintained until this time has elapsed.

Not Maintaining Setpoint: The “Not Maintaining Setpoint” detection is now the only thing that parameter P1-12 controls. Also, the
“Not Maintaining Setpoint” timer is held reset during the pre-charge function to prevent erroneous operation.

• P1-12 is only effective for the “Setpoint Not Met” fault.
• “Setpoint Not Met” is disabled during pre-charge.

Table 56 Parameters

Message Display

Description

Cause

Countermeasures

Net Pump Err Chk

Faulted Pump

Drive has been stopped because
another drive in the network has
a system fault (LOP, NMS,
HFB / HW, LFB / LW, LOWFL,
HIFLO, or ACCUM) or has the
Low City Pressure alarm.

Another drive in the network has a system fault (LOP,
NMS, HFB / HW, LFB / LW, LOWFL, HIFLO, or
ACCUM).

Check the drive that has the actual system fault and
either let the System Fault Retry function clear the
fault, or manually reset the faulted drive.

Another drive in the network has a Low City Pressure
alarm.

Check the drive that has the Low City Pressure alarm
and either reset the Low City Pressure digital input
(H1-0x = 73) or resolve the pressure situation.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P1-12

107

Not Maintaining Setpoint Time
Not Maint SP Tm

Delay time before a Not Maintaining Setpoint fault occurs. Pump
protection criteria specified in P1-11 must be met for the drive to
fault. On fault the drive will coast to a stop.
Setting P1-12 = 0 disables the Not Maintaining Setpoint fault

0 ~ 3600 s

60 s

Programming

TIME

Not Maintaining
Setpoint (NMS) Fault

Not Maintaining
Setpoint Time P1-12

P1-11

P1-11

SETPOINT

PRESSURE
FEEDBACK