Figure 132, P3-01 = 2: output frequency + feedback level – Yaskawa iQpump Controller Programming Manual User Manual

Page 176

Advertising
background image

176

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.128

Figure 132.

The pump system can be allowed to stabilize by programming a time into the Multiplex Stabilization Time (P3-11). The Multiplex
Stabilization Time (P3-11) becomes active after an auxiliary pump is staged or de-staged.

Note: The pump protection function is disabled during auxiliary pump staging and de-staging.

The No-Flow and Sleep functions are only active when the lead pump controlled by the drive is the only pump operating the pump
system.

P3-01 = 2: Output Frequency + Feedback Level

The “output frequency + feedback level” control method monitors the drive’s output frequency and the difference between the system’s
setpoint and feedback level to determine if the auxiliary pumps need to be staged (turned ON) to maintain the programmed system’s
setpoint. The output frequency and the difference between the system’s setpoint and feedback level also determine when the auxiliary
pumps are to be de-staged (turned OFF). Refer to

Figure 133.

and

Figure 134.

for the staging and de-staging of the auxiliary pumps using

the “output frequency + feedback level” control method.

Auxiliary Pump Staging (ON)

The staging of auxiliary pump 2 occurs when the output frequency remains above the iQpump drive Multi / Maximum Level (P3-02) and
the difference between the system’s setpoint and the feedback level exceeds the value programmed in the Add Pump Delta Level (P3-03)
for the time programmed in Add Pump Delay Time (P3-04).

The staging of auxiliary pump 3 occurs when the auxiliary pump 2 is staged and when the output frequency remains above the iQpump
drive Multi / Maximum Level (P3-02) and the difference between the system’s setpoint and feedback level exceeds the value programmed
in the Add Pump Delta Level (P3-03) for the time programmed in Add Pump Delay Time (P3-04). Refer to

Figure 133.

for the staging of

the auxiliary pumps using the “output frequency + feedback level” control method.

TIME

Feedback

Auto Mode Run

Multi-function

Output #40

0%

OFF Mode

Shutdown Pump

Delta Level P3-05

Start System, Incoming Run Command

Start System

System

Set-Point

Multi-function

Output #41

PUMP 1 + 2 + 3 RUNNING

Multiplex Stabilize Time

P3-11

Multiplex Stabilize Time

P3-11

Shutdown Pump Delta Level

P3-05

Shutdown Pump Delay Time

P3-06

Shutdown Pump Delay Time

P3-06

REMOVE PUMP 3

Open Contact

REMOVE PUMP 2

Open Contact