YASKAWA TM.iQp.07 iQpump Controller Programming Manual

U1-16

004F

Terminal A2 Input Voltage
Term A2 level

Displays the input current (or voltage) on Terminal A2, as a percentage of 20 mA (or 10 Vdc).

U1-18

0051

Motor Secondary Current (Iq)
Mot SEC Current

Displays the amount of current being used by the motor to produce torque (Iq).

U1-20

0053

Output Frequency After Soft
Start
SFS Output

Displays the frequency reference (speed command) after the accel and decel ramps.

U1-24

0057

PI Feedback Value
PI Feedback

Displays the feedback signal when PI control is used.

U1-28

005B

CPU Number
CPU ID

Displays control board hardware revision.

U1-29

005C

kWh
kWh Lo 4 Digits

Displays the accumulated kWh.

U1-30

005D

MWh
kWh Hi 5 Digits

Displays the accumulated MWh.

U1-34

0061

First Parameter Causing an OPE
OPE Detected

Displays the parameter number causing an “OPE” fault.

U1-36

0063

PI Input
PI Input

Displays the “error” in the PI regulator. (U1-36 = PI Set-point - PI Feedback).

U1-37

0064

PI Output
PI Output

Displays the output of the PI as a percentage of maximum frequency (E1-04).

U1-38

0065

PI Set-point
PI Set-point

Displays the setpoint of the PI regulator (U1-38 = PI reference + PI bias).

U1-39

0066

Memobus Communication Error
Code
Transmit Err

U1-40

0067

Heatsink Cooling Fan Operation
Time
FAN Elapsed Time

Displays total operating time of the heatsink cooling fan.

U1-62

007D

Running Queue No
Running Queue No

Position in the iQpump Memobus Multiplex Running Queue

U1-67

009B

Network Activity
Network Activity

Shows network traffic. A fluctuating number from 0 to 1000 denotes activity, while a
relatively constant 0 denotes no activity.
Unit changes based on network status:
<->: Drive can not communicate to other drives
<+>: Drive is a Node on a network
<M>: Drive is a Master on an iQpump Network

U1-68

0009C

Time to Alternate
Time to Alternate

Time remaining before a drive requests alternation which is dependent on P9-04.

U1-90

0720

Pump Set-point
Pump Set-point

Displays drive setpoint.
Resolution 0.1
Note:

Does not include setpoint compensation (U1-93).

U1-91

0721

Pump Feedback
Pump Feedback

Displays scaled feedback.
Resolution 0.1

Parameter No.

Addr.

Hex

Parameter Name Digital

Operator Display

Description

Monitor

1: CRC error

1: Data length error

Not used. Always 0.

1: Parity error

1: Overrun error

1: Framing error

1: Timeover

Not used. Always 0

.

0 0 0 0 0 0 0 0