Yaskawa iQpump Controller Programming Manual User Manual

Page 53

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

53

E1-04 Maximum Output Frequency

Setting Range:

0.0 ~ 120.0 Hz

Factory Default: 60.0 Hz

Refer to parameter E1-04 in Appendix A for description details.

E1-05 Maximum Output Voltage

Setting Ranges: 0.0 ~ 255.0 V (240 V Models)

0.0 ~ 510.0 V (480 V Models)

Factory Defaults: 240.0 V (240 V Models)

480.0 V (480 V Models)

Refer to parameter E1-05 in Appendix A for description details.

E1-06 Base Frequency

Setting Range:

0.0 ~ 120.0 Hz

Factory Default: 60.0 Hz

Refer to parameter E1-06 in Appendix A for description details.

E1-07 Mid Output Frequency A

Setting Range:

0.0 ~ 120.0 Hz

Factory Default: 3.0 Hz

Refer to parameter E1-07 in Appendix A for description details.

E1-08 Mid Output Voltage A

Setting Ranges: 0.0 ~ 255.0 V (240 V Models)

0.0 ~ 510.0 V (480 V Models)

Factory Defaults: 17.2 V (240 V Models)

34.5 V (480 V Models)

Refer to parameter E1-08 in Appendix A for description details.

E1-09 Minimum Output Frequency

Setting Range:

0.0 to 120.0 Hz

Factory Default: 1.5 Hz

Refer to parameter E1-09in Appendix A for description details.

E1-10 Mid Output Voltage

Setting Ranges: 0.0 ~ 255.0 V (240 V Models)

0.0 ~ 510.0 V (480 V Models)

Factory Defaults: 10.3 V (240 V Models)

20.7 V (480 V Models)

Refer to parameter E1-10 in Appendix A for description details.