Function description, Time – Yaskawa iQpump Controller Programming Manual User Manual

Page 191

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

191

Figure 1.142

Figure 146.

Function Description:

<0034>

Disable Low Pressure and Transducer Loss during Pre-charge. During the Pre-charge function, the low pressure and / or transducer loss
conditions will be ignored.

Two Stage Pre-charge. In order to get the Two Stage Pre-charge to operate, the normal Pre-charge function needs to be enabled, AND
parameter P4-12 needs to be set to a value greater than zero, AND parameter P4-13 must be set to a value greater than zero. When the
drive starts and is in Pre-charge Mode and the normal Pre-charge Timer expires (P4-02), the drive will switch to the P4-12 value for the
P4-13 time set. The functionality of the “Low Water” and “Disable Pre-charge” digital inputs are un-effected by the Two Stage
Pre-charge.

Run
Command

Hand Frequency

Pre-Charge
Frequency P4-02

Thrust Bearing
Frequency P4-05

Pre-Charge
Level P4-01

TIME

Thrust Bearing Mode and Pre-Charge Function with Alternating Auto and Hand Mode.

PI Feedback

Hand
Mode

Pre-Charge
Frequency P4-02

Thrust Bearing
Frequency P4-05

Standard
Accel Time
C1-01

Thrust
Bearing Accel
Time P4-04

Pre-Charge
Complete

Standard
Decel Time
C1-02

Thrust Bearing
Decel Time P4-06

Stop due to Run
Command Removed

Output Frequency

Frequency Reference
Limited because
Hand Frequency < P4-05

@ Hand
Frequency