164

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.117

Figure 121.

Total setpoint compensation can be monitored with Total Setpoint Compensation (U1-93).

P2-09 Setpoint Compensation

Setting Range:

0.0 ~ 6000.0

Factory Default: 0.0

The iQpump drive can automatically increase the setpoint each time the maximum number of cycles programmed in Sleep Mode:
Cycling Protection (P2-06). The units for this parameter are determined by the System Units (P1-02).

Refer to Over-Cycling Mode: (P2-08 = 3: Auto Compensation) for more details.

P2-10 Maximum Setpoint Compensation

Setting Range:

0.0 ~ 6000.0

Factory Default: 0.0

The iQpump drive can set the maximum allowable setpoint compensation during an over-cycling condition by the value programmed in
Maximum Setpoint Compensation (P2-10). The units for this parameter are determined by the System Units (P1-02).

Refer to Over-Cycling Mode: (P2-08 = 3: Auto Compensation) for more details.

P2-11 No-Flow Activation Level

Setting Range:

0 ~ 24000 rpm

Factory Default: 0 rpm

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). The no-flow
detection is active when the motor is operating below this No-Flow Activation Level (P2-11) and below the No-Flow Detection
Bandwidth (P2-12).

Setting P2-11 to a value of 0 will disable this function. This function is only active during operation in the Auto Mode and when the drive
is operating above the Minimum Pump Frequency (P1-06) and below the level programmed in P2-11.

Note: Program Start Level (P1-04) to a value greater than 0.

The No-Flow Activation Level (P2-11) works in conjunction with the No-Flow Detection Bandwidth (P2-12).

If P1-01 = 3, the function is active on the lead drive.

<0034>

TIME

System Running Auto Mode

Auto Mode Run

Sleep Mode

AUTO MODE

RUN

AUTO MODE

RUN

AUTO MODE

RUN

SLEEP

SLEEP

Cycle Count

Register

Cycle

Count = 1

Cycle

Count = 2

P2-06 Max. Cycle = 3
P2-09 Set-Point Comp = 1.0
P2-10 Max. SP Comp. = 10.0

Cycle

Count = 0

Cycle

Count = 1

Maximum cycle count exceeded,

Increase Set-Point with Value of P2-09.

Total Compensation not to exceed P2-10

SLEEP

Cycle

Count = 3

Cycle

Count = 2

INCR. SET-POINT by P2-09