Function: option / inv selection 1 (setting: 2), Function: multi-step sp1 (setting: 3), Function: multi-step sp2 (setting: 4) – Yaskawa iQpump Controller Programming Manual User Manual

Page 60

Advertising
background image

60

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Function: Option / Inv Selection 1 (Setting: 2)

The Option / Inv Selection function allows the user to select the source for the Run and speed commands between either the drive’s
terminals or an optional communication card. When a digital input is programmed for the Option / Inv Selection function (H1-0x = 2)
that input will function as follows:

Table 22 Digital Input Functions

To switch the command source between the option card and the terminals be sure to program the following parameters:

• Set b1-01 (Auto Setpoint Reference Selection) to 1 (Terminals).
• Set

(Run Command Selection) to 1 (Terminals).

• Set H1-0x (Input Terminal Function Selection) to 2.

Important: Switching between the different Reference and Run sources can only be done while the iQpump drive is stopped.

Function: Multi-step SP1 (Setting: 3)

Function: Multi-step SP2 (Setting: 4)

The iQpump drive can be programmed to step through four preset setpoints and a jog reference. It is also possible to mix in the analog
inputs as setpoint references that can be chosen in place of the first and second preset setpoint references. The selection of which preset
setpoint will be the active setpoint is determined by the status of the digital inputs set for Multi-step SP1 (H1-0x = 3) and Multi-step SP2
(H1-0x = 4). Changing the active setpoint via the Multi-step Setpoint References can be done while the iQpump drive is running.

The following table details which reference is active based on the status of the Multi-step SP1 and Multi-step SP2 inputs:

Table 23 Digital Input Functions

The determination of whether the Preset Reference 1 will be the Setpoint Reference 1 (d1-01 or the analog input A1) is determined by the
status of b1-01. If b1-01 = “1: Terminals,” the value of the input to A1 will determine the commanded Setpoint when Preset Reference 1
is selected. If b1-01

≠1, the setting of d1-01 will determine the commanded Setpoint when Preset Reference 1 is selected.

The determination of Preset Reference 2 is made much the same way as Preset Reference 1 except that the setting of parameter H3-09
decides whether the analog input A2 or d1-02 is Preset Setpoint 2. If H3-09 = “2: Aux Reference,” the value of the input to A2 will
determine the commanded Aux Reference when Preset Reference 2 is selected. If H3-09 = 2, the setting of d1-02 will determine the
commanded setpoint when Preset Reference 2 is selected.

Option / Inv Selection Input Status

Run and Speed Command Source

CLOSED

From the control circuit and analog input terminals

OPEN

From the Communications Option Card

Preset Reference

Terminal Programmed

as Multi-step SP1

Terminal Programmed

as Multi-step SP2

Details

1

OFF

OFF

Setpoint Reference 1 (d1-01) or analog input A1#

(determined by b1-01)

2

ON

OFF

Setpoint Reference 2 (d1-02) or analog input A2#

(determined by H3-09)

3

OFF

ON

Setpoint Reference 3 (d1-03)

4

ON

ON

Setpoint Reference 4 (d1-04)

#

Shown for H3-13 = “0: Main Fref TA1”; A1 and A2 are reversed if H3-13 = “1: Main Fref TA2”

Advertising