P2-12 no-flow detection bandwidth – Yaskawa iQpump Controller Programming Manual User Manual

Page 166

Advertising
background image

166

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.119

Figure 123.

P2-12 No-Flow Detection Bandwidth

Setting Range:

0 ~ 1000 rpm

Factory Default: 15 rpm

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). The no-flow
activation can have a programmed bandwidth before the no-flow condition is activated by programming the No-Flow Detection
Bandwidth (P2-12).

The No-Flow Detection Bandwidth (P2-12) sets the motor rpm fluctuation bandwidth. The no-flow detection activates when the motor
rpm is below the No-Flow Activation Level (P2-11) and remains within the programmed No-Flow Detection Bandwidth (P2-12) for a
time specified by the No-Flow Detection Time (P2-13).

The No-Flow Detection Bandwidth (P2-12) works in conjunction with the No-Flow Activation Level (P2-11).

Refer to the No-Flow Activation Level (P2-11) for more details.

Note:

Sleep function P2-02 is enable (P2-02 > 0)