L5 fault restart, L5-01 number of auto restart attempts, L5-02 auto restart operation selection – Yaskawa iQpump Controller Programming Manual User Manual

Page 123: L5-03 maximum restart time after fault

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

123

L5 Fault Restart

L5-01 Number of Auto Restart Attempts

Setting Range:

0 ~ 10

Factory Default: 5

Refer to parameter L5-01 in Appendix A for description details.

L5-02 Auto Restart Operation Selection

L5-03 Maximum Restart Time After Fault

Setting Range:

10.0 ~ 3600.0 s

<0032>

Factory Default: 20.0 s

All major faults will cause the iQpump drive to stop. For some faults it is possible to configure the iQpump drive to attempt a restart
automatically. After the fault occurs, the iQpump drive baseblocks for the Maximum Restart Time After Fault programmed in L5-03.
After the baseblock is removed the iQpump drive checks if a fault condition still exists. If no fault condition exists the iQpump drive will
attempt to restart the motor. If the restart is successful, the iQpump drive performs a Speed Search (Regardless of the status of b3-01
“Speed Search Selection”) from the set speed command and the Auto Restart Attempts count is increased by one. Even if the restart fails
the restart count is increased by one as long as the iQpump drive attempted to rotate the motor. The restart count will not be incremented
if the restart is not attempted due to a continuing fault condition, (i.e. an OV fault). The iQpump drive waits the Maximum Restart Time
After Fault (L5-03) before attempting another restart. This parameter is not applicable to Loss of Prime Fault.

Figure 1.101

Figure 105. Automatic Restart Timing Diagram

The auto restart count is reset back to 0 if any of the following occur:

• No further faults for ten minutes after the last retry.
• The drives power is turned off (the iQpump drive must be without power long enough to let control power dissipate).
• The SHIFT / RESET key is pushed after the last reset attempt.

Setting

Description

0

No Flt Relay (

factory default

)

1

Flt Relay Active

t

t

t

t

Run

Fault

Attempts

Count

L2-03

OV

trying each

L5-03 seconds successful

1

OC

L2-03

2

Voltage
remains high
for a long time,
then reset (1)

L2-03

3

OC

OC condition
gone, resets (3)
and runs.

successful

try but failed

Drive trips on OC,
resets (2) and tries
again but motor still
shorted, trips again.

TIME

Advertising