P2-21 sleep boost level, P2-22 sleep boost maximum time, P2-23 anti-no flow bandwidth – Yaskawa iQpump Controller Programming Manual User Manual

Page 170

Advertising
background image

170

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

• P2-01 = 1: Display based on “Hz”

<0034>

• P2-01 = 2: Display based on “Hz”

<0034>

• P2-01 = 3: Display based on “rpm”

<0034>

• P2-01 = 4: Display based on “Hz”

<0034>

The Alternative Sleep Activation Level (P2-20) works in conjunction with the Start Level (P1-04) and the Sleep Level Type (P2-01).

It is recommended that P2-20 be programmed 1 or 2 Hz above the P1-06 value. The sleep level using P2-20 enables the sleep mode;
however, the drive still enters sleep based on P2-20. With the normal default sleep level programmed in
P2-02, the sleep cycle will not activate until the output frequency is above P2-02.

P2-21 Sleep Boost Level

<0034>

Setting Range:

0.0 ~ 6000.0

Factory Default: 0.0

Refer to parameter P2-21 in Appendix A for description details.

P2-22 Sleep Boost Maximum Time

<0034>

Setting Range:

1.0 ~ 160.0 s

Factory Default: 5.0 s

Refer to parameter P2-22 in Appendix A for description details.

P2-23 Anti-No Flow Bandwidth

<0034>

Setting Range:

0.00 ~ 2.00%

Factory Default: 0.40%

The iQpump P2-23 parameter is to provide a simple and reliable method of detecting and reacting to the “No-Flow” condition. When the
drive detects that the pump is no longer contributing to the overall pressure in the system due to a “No-Flow” condition, an increased rate
of deceleration will occur. The normal sleep function will then take over. This function will only operate when the Sleep Level Type is
frequency or speed (P2-01 = 3).

Figure 1.123

Figure 127. Anti-No-Flow

PI

Feedback

Output

Frequency

Anti No Flow

P2-24

ANF Det Time

PI

Setpoint

P2-03

Sleep Tm.

Output Frequency if Anti-No-Flow

disabled.

Drive

(re)Start

Start of No-Flow

Condition

P2-02

Sleep Level

Min Speed or

Thrust Speed

are