H1 Digital Inputs

Terminal Function Selections

Setting Range:

0 ~ 86

Factory Defaults: H1-01 = “24: External Fault”

H1-02 = “14: Fault Reset”
H1-03 = “3: Multi-Step SP1” (2-Wire)

xxxxxxx

“0: 3-Wire Control” (3-Wire)

H1-04 = “80: Hand Mode”
H1-05 = “84: Pre-charge”

The iQpump drive has five multi-function contact digital inputs. By programming parameters H1-01 through H1-06, the user can assign
specific functions to each input. Below is a table with a complete list of all of the digital input functions. Following the table is a more
detailed description of each of the functions.

Table 20 Digital Input Functions

* Input Level Sel - H1-0x = 35, This multi-function input selection for PI Invert has been removed because it interferes with the standard
iQpump operation.

<0034>

Parameter No.

Parameter Name

H1-01

Terminal S3 Function Selection

H1-02

Terminal S4 Function Selection

H1-03

Terminal S5 Function Selection

H1-04

Terminal S6 Function Selection

H1-05

Terminal S7 Function Selection

Parameter setting

Function

Parameter setting

Function

0

3-Wire Control

20-2F

External Pump Fault

1

Local / Remote Selection

30

Integral Reset

2

Option / Inv Selection 1

31

Integral Hold

3

Multi-step SP1

34

PI Soft Start Cancel

4

Multi-step SP2

-

-

6

Not Used

36

Option / Inv Selection 2

7

Multi-Accel / Decel 1

60

Motor Pre-heat

8

External Baseblock N.O.

61

Speed Search 1

9

External Baseblock N.C.

62

Speed Search 2

A

Accel / Decel Ramp Hold

64

Speed Search 3

C

Terminal A2 Enable

67

Communications Test Mode

F

Terminal Not Used

68

High Slip Braking

10

MOP Increase

6A

Drive Enable

11

MOP Decrease

6B

Comm / Inv Selection

12

Not Used

6C

Com / Inv SEL 2

13

Not Used

6D

Not Used

14

Fault Reset

6E

Not Used

15

Fast Stop N.O.

70

Not Used

17

Fast Stop N.C.

80

Hand Mode

18

Timer Function

81

Disable Sleep Mode

19

PI Disable

82

Sleep Activation

1B

Program Lockout

83

Thermostat Fault

1C

Not Used

84

Disable Pre-charge

1D

Not Used

85

Low Water Level

1E

Not Used

86

Fixed Speed Auto

Advertising