Yaskawa iQpump Controller Programming Manual User Manual

Page 244

Advertising
background image

244

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

P9-08 = 2: Feedback + Output Frequency:

This mode monitors both the feedback level and the output frequency to determine if staging is needed. When the output frequency rises
above the P9-09 level and the delta feedback (setpoint - feedback) has exceeded the level set in P9-10 for the time set in P9-11, the lead
drive will issue a network stage request if there is a drive available to run. Refer to

Figure 186.

De-staging:

P9-12 = 0: Output Frequency:

This mode monitors the lead drive output frequency and determines if de-staging is needed to maintain the setpoint. If the output
frequency of the lead drive drops below the P9-13 level for the time set in P9-15, then a de-stage request is issued if this is not the only
drive running. Refer to

Figure 187.

P9-12 = 1: Feedback Level:

This mode monitors the feedback level and determines if de-staging is needed. If the difference in feedback and setpoint (feedback -
setpoint) has exceeded the P9-14 level for the time set in P9-15, then a de-stage request is issued if this is not the only drive running.
Refer to

Figure 188.

P9-12 = 2: Feedback + Output Frequency:

This mode monitors both the feedback level and the output frequency to determine if de-staging is needed. the output frequency of the
lead drive drops below the P9-13 level and the delta feedback (feedback - setpoint) has exceeded the P9-14 level for the time set in P9-15,
then a de-stage request is issued if this is not the only drive running. Refer to

Figure 189.

Quick De-stage (P9-18 x P1-09 < PI Feedback):

If the feedback level goes above P9-18 (set as a percentage of P1-09) for 2 seconds, a de-stage request is issued if this is not the only drive
running. Refer to

Figure 190.

If Stabilize Time P9-16 > 0, then whenever a pump becomes a lag drive, or gets de-staged that disables lead-lag control and pump
protection. It will resume these functions when the timer P9-16 expires, which counts only when the drive becomes a lead drive once
again.

Setpoint Modifier P9-17 is used to increase or decrease the setpoint each time an additional pump is brought online to compensate for
system losses or gains. The drive's setpoint is modified using this calculation:

Pump X: Setpoint + ((X-1)(P9-17))

Thus, if there is only one pump running, the setpoint is not modified.

Monitor U1-62 is only available when P1-01 = 3. The monitor displays the drive’s network run queue number. The first drive to run will
show U1-62 = 1, the second drive U1-62 = 2 and so on.

When P1-01 = 3 (MEMOBUS / Modbus Network), the U1-01 Display text will change depending on the Auto Mode run command and
the network run command as can be seen in

Table 117 on page 245

.

Advertising