If p2-01 = “3: output speed (rpm), Figure 117. sleep function based on feedback level – Yaskawa iQpump Controller Programming Manual User Manual

Page 158

Advertising
background image

158

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.113

Figure 117. Sleep Function Based on Feedback Level

If P2-01 = “3: Output Speed (rpm)”

<0034>

The iQpump drive can be configured to enter a “sleep” condition based on the feedback signal. The drive will enter the sleep mode when
the feedback signal rises above the programmed Sleep Level (P2-02) for a time specified by the Sleep Delay Time (P2-03).

If P2-01 = “4: Low Flow (Terminal A1 - Flow meter required)”

<0034>

The iQpump drive can be configured to enter a “sleep” condition based on the feedback signal. The drive will enter the sleep mode when
the feedback signal rises above the programmed Sleep Level (P2-02) for a time specified by the Sleep Delay Time (P2-03).

Figure 1.114

Figure 118. Sleep Boost: Feedback reaches boosted setpoint

Sleep Delay Time

P2-03

Run Cmd.

PI Setpoint

Output

requency

P1-05

S-Lvl Delay Time

P2-03

Sleep Delay Time

Sleep Boost Lvl (P2-21)

PI

Feedback

PI Setpoint

Start Level (P1-04)

Sleep Boost Lvl (P2-21)

0.5 sec

P2-22

Sleep Boost Time

Sleep

Active

P2-02

Sleep Level