Drive 1 drive 2 drive 3, Drive 4, Figure 180. alternation mode is fifo forced – Yaskawa iQpump Controller Programming Manual User Manual

Page 237

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

237

Figure 1.176

Figure 180. Alternation Mode is FIFO Forced

PumpNet Control 1 U1-xx bit 1:

Run as Lag Drive

PumpNet Control 1 U1-xx bit 2:

Run as Lead Drive

PumpNet Control 1 U1-xx bit 1:

Run as Lag Drive

PumpNet Control 1 U1-xx bit 2:

Run as Lead Drive

PumpNet Control 1 U1-xx bit 1:

Run as Lag Drive

PumpNet Control 1 U1-xx bit 2:

Run as Lead Drive

Drive 1

Drive 2

Drive 3

Alternation Timer P

9-03

PumpNet Status 1 U1-xx bit 7:

Request for FIFO Forced Alternation

PumpNet Status 1 U1-xx bit 7:

Request for FIFO Forced Alternation

PumpNet Control 1 U1-xx bit 1:

Run as Lag Drive

PumpNet Control 1 U1-xx bit 2:

Run as Lead Drive

Drive 4

PumpNet Status 1 U1-xx bit 7:

Request for FIFO Forced Alternation

PumpNet Status 1 U1-xx bit 7:

Request for FIFO Forced Alternation

Alternation Timer P9-03

Network Processing

& Delay

Network Processing

& Delay

Drive 1 is the

First Pump

Drive 2 is now the First Pump

Drive 4 is forced to be the new

Lead Drive (P9-01 determined ,

and only drive available )

Drive 3 is now the First Pump

Drive 4 is again forced to be

the new Lead Drive (P9-01

determined )