Yaskawa iQpump Controller Programming Manual User Manual

Page 192

Advertising
background image

192

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.143

Figure 147. Two Stage Pre-charge - Pre-charge Timer

Figure 1.144

Figure 148. Two Stage Pre-charge - Feedback reaches Pre-charge Level

Table 71 Related Parameters

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P4-01

115

Pre-charge Level
Pre-charge Level

When enabled drive will run at P4-02 Frequency. The drive will stop
when one of the following conditions occurs: Feedback signal rises
above P4-01 Level, pre-charge timer P4-03 expires or Low Water
digital input is deactivated (#85).

0.0 ~

6000.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Programming

P4-02

116

Pre-charge Frequency
Pre-charge Freq

Frequency reference used when Pre-charge function is active.

0.00 ~

120.00 Hz

0.00 Hz Programming

P4-03

117

Pre-charge Time
Pre-charge Time

Maximum allow Pre-charge Time.

A value of 0 disables this function.

0.0 ~

3600.0 min 0.0 min Programming

Output

Frequency

Run

Command

P4-13

Pre-charge Time 2

P4-03

Pre-charge Time

Feedback

Level

P4-01 Pre-charge Level

P4-12
Pre-charge Freq 2

P4-02

Pre-charge Freq .

Pre-Charge

D.O.

Output

Frequency

Run

Command

P4-03

Pre-charge Time

Feedback

Level

P4-01 Pre-charge Level

P4-12

P4-02

Pre-charge Freq .

Pre-Charge

D.O.

P4-13

Pre-charge Time 2