B5-02 proportional gain setting, Figure 28. dual zone pi operation – Yaskawa iQpump Controller Programming Manual User Manual

Page 35

Advertising
background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

35

Figure 1.28

Figure 28. Dual Zone PI Operation

Table 8 Related Parameters

<0034>

Table 9 Parameters

<0034>

Table 10 Fault

<0034>

b5-02 Proportional Gain Setting

Setting Range:

0.00 ~ 25.00

Factory Default: 2.00

The proportional gain will apply a straight multiplier to the calculated difference (error) between the PI Setpoint and the measured
transmitter feedback at terminal A2. A large value will tend to reduce the error but may cause instability (oscillations) if too high. A small
value may allow to much offset between the setpoint and feedback (See

Figure 29.

on following page).

Parameter

No.

Addr. Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

d1-02



281

Setpoint 2
Setpoint 2

Digital preset setpoint 2. Used when b1-01 = 0. Setting units are
affected by P1-02 and P1-03. Also is the Zone 1 PI reference when
b5-01 = 2.

0.00 ~

P1-02

value

0.00

Programming

d1-03



282

Setpoint 3
Setpoint 3

Digital preset setpoint 3. Used when b1-01 = 0. Setting units are
affected by P1-02 and P1-03. Also is the Zone 2 PI reference when
b5-01 = 2.

0.00 ~

P1-02

value

0.00

Programming

d1-04



283

Setpoint 4
Setpoint 4

Digital preset setpoint 4. Used when b1-01 = 0. Setting units are
affected by P1-02 and P1-03. Also is the Zones 1 and 2 PI reference
when b5-01 = 2.

0.00 ~

P1-02

value

0.00

Programming

 Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr. Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

P4-17

<0034>

830

Dual Zone PID Feedback
Bandwidth Range
Dual Zone Range

Determines the detection bandwidth for the dual zone PI control.

0 ~ 6000.0

(system

units

P1-02)

10.0

(system

units

P1-02)

Programming

Fault Display

Description

Cause

Countermeasures

oPE13

Terminal A1

Programming error

Terminal A1 is being assigned to more than one of the following
functions:
- Frequency Reference (b1-01 = 1)
- Dual Zone PI is enabled (b5-01 = 2)
- Flow Meter Enabled (P6-01 > 0)
- Level Control Enabled (P8-01 = 1)

Reprogram b1-01, b5-01, P6-01,
or P8-01.

Run Cmd.

PI Setpoint

PI

Feedback

Zone 1

(Term A1)

PI Feedback

Zone 2

(Term A1)

PI Feedback

5 sec

5 sec

Short

Disturbance

Zone 1 Valve

Is closed

5 sec

Zone 2 Valve

Is opened

5 sec

Zone 2 Valve

Is closed

5 sec

Zone 1 Valve

Is opened

d1-04

d1-04

d1-04

d1-02

d1-03