P2-02 Sleep Level

Setting Range:

0.0 ~ 6000.0

Factory Default: 0.0

P2-20



Sleep Activate Level
SLP Act. Level

When P2-01 Sleep Level Type is set for 0 (Output Frequency) or 3
(Output Speed). The sleep function becomes active when output
frequency is greater or equal to the level P2-20. When programmed
to 0, sleep function will become active in above P2-02 Sleep Level.

Display Units for Sleep Level P2-20:

P2-01 = 0, => “Hz”
P2-01 = 1, => “Hz”
P2-01 = 2, => “Hz”
P2-01 = 3, => “rpm”
P2-01 = 4, => “Hz”
A value of 0 disables this function.

0.0 ~

6000.0

0.0

Programming

P4-04

Thrust Bearing Acceleration
Time
Thrust Acc Time

When enabled (P4-05>0) the drive output frequency will ramp up to
the specified reference frequency in P4-05 in the time specified in
P4-04. <1> PI mode is automatically disabled.

0 ~ 600.0 s

1.0 s

Programming

P4-06

Thrust Bearing Deceleration
Time
Thrust Dec Time

This is the amount of time that it will take to bring the drive from
Thrust Frequency (P4-05) to stop when Thrust Mode is active. Any
time the Run Command is removed while the drive is operating in
Thrust Mode above the Thrust Frequency, this deceleration time will
be used once the frequency reference is at or below the Thrust
Frequency.

0 ~ 600.0 s

1.0 s

Programming



Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P1-16



87F

Loss of Prime Time
Prime Loss Time

Delay time before a Loss of Prime fault occurs. Pump protection
criteria specified P1-14 must be met for the drive to fault. On fault the
drive will coast to a stop.

1 ~ 600 s

20 s

Programming

P2-21

820

Sleep Boost Level
Sleep Boost Lvl

Sets the amount of boost applied to the setpoint just before going to
sleep. A setting of 0.0 disables the sleep boost function. (Internally
limited to 25% of P1-03).

0.0 ~

6000.0

(system

units

P1-02)

0.0

Programming

P2-22

821

Sleep Boost Maximum Time
Sleep Boost Time

Sets the amount of time the system (feedback) has to reach the
“boosted” setpoint. If more than this time elapses, the drive will go to
sleep.

1.0 ~

160.0 s

5.0

Programming



Denotes that parameter can be changed when the drive is running.

Message Display

Description

Sleep Boost Active

The drive is entering the sleep mode and the pressure setpoint is being boosted.
During this time, the U1-01 monitor will be updated with the boosted setpoint.

Alarm Display

Description

Countermeasures

Freq. Ref <

Pump Min P1-06

The drive's frequency reference is set less than the Minimum Pump Frequency P1-06.
The frequency reference will be lower-limited to P1-06 during this time.

This will only be active when:
-Drive is NOT in PI mode
-Drive is running
-Minimum Pump Frequency is enabled (P1-06 > 0.00)

Increase the frequency reference to a value greater
than P1-06.

Freq. Ref <

Thrust P4-05

The drive's frequency reference is set less than the Thrust Bearing Frequency P4-05. The
frequency reference will be lower-limited to P4-05 during this time.

This will only be active when:
-Drive is NOT in PI mode
-Drive is running
-Thrust Bearing is enabled (P4-05 > 0.00)

Increase the frequency reference to a value greater
than P4-05.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu