H5-01 drive node address, H5-02 communications speed selection, H5-03 communications parity selection – Yaskawa iQpump Controller Programming Manual User Manual

Page 108

Advertising
background image

108

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

MEMOBUS / Modbus Self-Diagnosis

The iQpump drive has a built-in function for self-diagnosing the operations of serial communication interface circuits. The self-diagnosis
function connects the communication parts of the send and receive terminals, receives the data sent by the drive, and checks if
communication is being performed normally.

Perform the self-diagnosis function using the following procedure.

1. Turn ON the power supply to the drive, and set parameter H1-05 (Terminal S7 Function Selection) to 67 (Comm Test Mode).
2. Turn OFF the power supply to the drive.
3. Perform wiring according to the following diagram while the power supply is turned OFF.
4. Turn ON the terminating resistance. (Turn ON pin 1 on DIP switch 1.)
5. Turn ON the power supply to the iQpump drive again.

Figure 1.91

Figure 95. Communication Terminal Connection for Self -Diagnosis Function

6. During normal self-diagnostic operation, the Digital Operator displays the frequency reference value. If an error occurs, a CE

(MEMOBUS / Modbus communication error) alarm will be displayed on the Digital Operator, the fault contact output will be turned
ON, and the iQpump drive operation ready signal will be turned OFF.

H5-01 Drive Node Address

In order for a master to be able to communicate with the iQpump drive using serial communications, the iQpump drive must have a
unique node address. The iQpump drive is given a node address if H5-01

0. The node addresses do not have to be assigned in sequential

order but they must be unique, i.e. no two drives on the same serial network can be assigned the same address. After setting the iQpump
drive address with the H5-01 parameter, the power to the iQpump drive must be cycled for the addressing to take effect.

Leaving H5-01 = 0 will disable responses to MEMOBUS / Modbus communications.

H5-02 Communications Speed Selection

H5-03 Communications Parity Selection

Parameters H5-02 and H5-03 configure the drives MEMOBUS / Modbus communications via the RS-485 / 422 terminals on the
removable terminal block. Configure H5-02 and H5-03 to match the settings of the master controller of the serial network. After changing
the H5-02 or H5-03 parameter, the power to the iQpump drive must be cycled for the change to take effect.

If either the speed or parity value is changed via the serial communications, the serial communications will cease to operate until the
iQpump drive power is cycled.

It may be necessary to avoid the 19.2 K baud setting if frequent serial communications errors occur at that baud rate.

Setting Range: 0 ~ 20 (Hex)

} MODBUS

0 ~ FF

} N2

0 ~ 63

} P1

Factory Default:

1F

1F

1F

Setting

Description

0

1200 Baud

1

2400 Baud

2

4800 Baud (Standard for APOGEE)

3

9600 Baud (

factory default

) (Standard for Metasys)

4

19200 Baud

Setting

Description

0

No Parity (

factory default

)

1

Even Parity

2

Odd Parity

Advertising