YASKAWA TM.iQp.07 iQpump Controller Programming Manual

289

P9-04

<0034>

0883

Alternation Mode
Alternation Mode

Determines how alternation is performed:
0: FIFO Auto
1: FIFO Forced
2: LIFO

0 ~ 2

0

Programming

P9-05

<0034>

0884

Lag Drive Mode
Lag Drive Mode

Determines how the lag drives function.
0: Fixed Speed - Runs at the P9-06 setting.
1: PI Regulation - Uses PI to determine speed.

0 ~ 1

0

Programming

P9-06



<0034>

0885

Lag Fixed Speed
Lag Fixed Speed

When the drive changes from a lead to a lag and P9-05 = 0, the drive
will run at this speed after P9-07 delay time expires.

0.0 ~

120.0 Hz

55.0 Hz Programming

P9-07



<0034>

0886

Lag Fixed Speed Delay
Lag Fixed Spd

Dly

When the drive changes from a lead to a lag and P9-05 = 0, this time
specifies how long before the drive runs at the P9-06 speed.

0 ~ 1000 s

5 s

Programming

P9-08

<0034>

0887

Add Pump Mode
Add Pump Mode

Selects the detection method for staging a new pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout

0 ~ 2

0

Programming

P9-09



<0034>

0888

Add Freq Level
Add Freq Lvl

When P9-08 = 0 and the output frequency rises above this level for the
time set in P9-11, the lead drive will request for a new lead drive
through the iQpump Memobus Network.

When P9-08 = 2 and the output frequency rises above this level the
delta feedback (setpoint - feedback) has exceeded the level set in
P9-10 for the time set in P9-11, the lead drive will request for a new
lead drive through the iQpump Memobus network.

0.0 ~

120.0 Hz

56.0 Hz Programming

P9-10



<0034>

0889

Add Delta Level
Add Delta Lvl

When P9-08 = 1 and the delta feedback (setpoint - feedback) has
exceeded this level for the time set in P9-11, the lead drive will request
for a new lead drive through the iQpump Memobus Network.

When P9-08 = 2 and the delta feedback (setpoint - feedback) has
exceeded this level and the output frequency is above P9-09 for the
time set in P9-11, the lead drive will request for a new lead drive
through the iQpump Memobus network.

0 ~ 6000.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Programming

P9-11



<0034>

088A

Add Delay Time
Add Dly Time

Delay time before a new lead drive is added to the system.

0 ~ 3600 s

10 s

Programming

P9-12

<0034>

088B

Remove Pump Mode
Remove Pump Mode

Selects the detection method for de-staging to the previous lead pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout

0 ~ 2

0

Programming

P9-13



<0034>

088C

Remove Freq Level
Remove Freq Lvl

When P9-12 = 0 and the output frequency drops below this level for
the time set in P9-15, the lead drive will request to be removed from
the system through the iQpump Memobus network.

When P9-12 = 2 and the output frequency drops below this level and
the delta feedback (feedback - setpoint) has exceeded the level set in
P9-14 for the time set in P9-15, the lead drive will request to be
removed from the system through the iQpump Memobus network.

0.0 ~

120.0 Hz

40.0 Hz Programming

P9-14



<0034><003

4>

088D

Remove Delta Level
Remove Delta Lvl

When P9-12 = 1 and the delta feedback (feedback - setpoint) has
exceeded this level for the time set in P9-15, the lead drive will request
to be removed from the system through the iQpump Memobus
network.

When P9-12 = 2 and the delta feedback (feedback - setpoint) has
exceeded this level and the output frequency is below P9-13 for the
time set in P9-15, the lead drive will request to be removed from the
system through the iQpump Memobus network.

0 ~ 6000.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Programming

P9-15



<0034>

088E

Remove Delay Time
Remove Dly Time

Delay time before the lead drive is removed from the system.

0 ~ 3600 s

10 s

Programming

P9-16



<0034>

088F

Stabilization Time
Stabilization Time

Time used to stabilize the system when a pump is staged or de-staged.
Lead-lag control and pump protection is suspended during this time.

0 ~ 3600 s

3 s

Programming



Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.