YASKAWA TM.iQp.07 iQpump Controller Programming Manual

59

Table 21 Parameters

<0034>

Function: 3-Wire Control (Setting: 0)

When one of the digital inputs is programmed for 3-Wire control, that input becomes a Forward / Reverse directional input. Whenever the
input is open, the iQpump drive will be set for forward rotation of the motor shaft. If the input it closed, then the motor shaft will rotate in
the reverse direction whenever a there is a Run input. The S1 and S2 digital inputs will function as a Run and Stop input respectively.

Figure 1.39

Figure 39. Terminal Configuration for 3-Wire Control

Figure 1.40

Figure 40. 3-Wire Control Timing Diagram

Important: As long as the S1(Run Command) input is applied in for at least 50 ms the Run command will latch internally in the drive.

Function: Local / Remote Selection (Setting: 1)

This function has been disabled. Please refer to settings “6D” and “6E”.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

H1-12

87A

External Fault 3 Delay Time
EF3 Delay Time

Sets the amount of time delay applied to the EF3 fault.
(20 =< H1-01 =< 2F)

0.00 ~

300.00

0.00 s

Programming

H1-13

87B

External Fault 4 Delay Time
EF4 Delay Time

Sets the amount of time delay applied to the EF4 fault.
(20 =< H1-02 =< 2F)

0.00 ~

300.00

0.00 s

Programming

H1-14

87C

External Fault 5 Delay Time
EF5 Delay Time

Sets the amount of time delay applied to the EF5 fault.
(20 =< H1-03 =< 2F)

0.00 ~

300.00

0.00 s

Programming

H1-15

87D

External Fault 6 Delay Time
EF6 Delay Time

Sets the amount of time delay applied to the EF6 fault.
(20 =< H1-04 =< 2F)

0.00 ~

300.00

0.00 s

Programming

H1-16

87E

External Fault 7 Delay Time
EF7 Delay Time

Sets the amount of time delay applied to the EF7 fault.
(20 =< H1-05 =< 2F)

0.00 ~

300.00

0.00 s

Programming

3-wire control

Stop switch
(NC contact)

Operation switch
(NO contact)

Run command
(run on momentary close)
Stop command
(stop on momentary open)

Sequence input common

SN

50 ms min.

Run command

Forward/reverse
command

Motor speed

Can be either ON or OFF

OFF
(stopped)

OFF (forward)

ON (reverse)

Stop

Forward

Reverse

Stop

Forward

Stop command

TIME