Yaskawa iQpump Controller Programming Manual User Manual
Page 75

YASKAWA TM.iQp.07 iQpump Controller Programming Manual
75
Figure 1.61
Figure 61. External Fault 3 - Normally Open, Detected During Run, Coast To Stop
Figure 1.62
Figure 62. Normally Closed, Detected During Run, Coast To Stop
EF3 Input
(H1-01 = 26)
External Fault 3 – Normally Open, Detected During Run, Coast To Stop
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
Fault Reset
Input
Run
Command
Output
Frequency
Fault Output
(External Fault 3)
EF3 Input
(H1-01 = 26)
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
Fault Reset
Input
Run
Command
Output
Frequency
Fault Output
(External Fault 3)
EF3 Input
(H1-01 = 27)
External Fault 3 – Normally Closed, Detected During Run, Coast To Stop
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
Fault Reset
Input
Run
Command
Output
Frequency
Fault Output
(External Fault 3)