YASKAWA TM.iQp.07 iQpump Controller Programming Manual

273

H5-06

042A

Drive Transmit Wait
Time
Transmit WaitTim

Sets the time from when the drive receives data to when the drive sends
data.

5 ~ 65 ms

5 ms

Programming

109

H5-07

042B

RTS Control Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:

0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 ~ 1

1

Programming

109

H5-08

042C

Communication Protocol
Selection
Com Protocol Sel

0: MEMOBUS / Modbus
1: N2 (Metasys)
2: FLN (APOGEE)

0 ~ 2

0

Programming

109

H5-09

0435

Communication Error
Detection Time
CE Detect Time

Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and H5-04.

0.0 ~

10.0 s

2.0 s

Programming

Motor Overload

L1-01

0480

Motor Overload
Protection Selection
MOL Flt Sel

Enables or disables the motor thermal overload protection.

0: Disabled
1: Std Fan Cooled (Enabled)
2: Std Blower Cooled
3: Vector Motor

0 ~ 1

1

Programming

114

L1-02

0481

Motor Overload
Protection Time
MOL Time Const

Determines how much time will elapse prior to a motor overload fault
(OL1), when motor amps exceed the value set in parameter E2-01 by
10 % . Actual (OL1) trip time will vary depending on severity of
overload.

0.1 ~

20.0 min

8.0 min Programming

114

L1-03

0482

Motor Overheat Alarm
Operation Selection
Mtr OH Alarm Sel

Operation selection when the motor temperature analog input

(H3-09 = E) exceeds the OH3 alarm level (1.17 V)

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 ~ 3

3

Programming

115

L1-04

0483

Motor Overheat Fault
Operation Selection
Mtr OH Fault Sel

Stopping method when the motor temperature analog input
(H3-09 = E) exceeds the OH4 level (2.34 V).

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop

0 ~ 2

1

Programming

115

L1-05

0484

Motor Temperature Input
Filter Time
Mtr Temp Filter

Delay Time applied to motor temperature analog input (H3-09 = E) for
filtering purposes.

0.00 ~

10.00 s

0.20 s

Programming

115

Power Loss Ridethru

L2-01

0485

Momentary Power Loss
Detection Selection
PwrL Selection

Enables and disables the momentary power loss function.

0: Disabled - Drive trips on (UV1) fault when power is lost.
1: PwrL Ride Thru t - Drive will restart if power returns within the time
set in L2-02.*
2: CPU Power Active - Drive will restart if power returns prior to
internal power supply shut down.*

* In order for a restart to occur, the run command must be maintained
throughout the ride thru period.

0 ~ 2

2

Programming

117

L2-02

0486

Momentary Power Loss
Ride-thru Time
PwrL Ridethru T

Determines the power loss ride-thru time. This value is dependent on
the capacity of the drive. Only effective when L2-01 = 1.

0.0 ~

25.5 s

kVA

Dependent

Programming

117

L2-03

0487

Momentary Power Loss
Minimum Base Block
Time
PwrL Baseblock T

Used to allow the residual motor voltage to decay before the drive
output turns back on. After a power loss, if L2-03 is greater than L2-02,
operation resumes after the time set in L2-03.

0.1 ~ 5.0 s

kVA

Dependent Programming

117

L2-04

0488

Momentary Power Loss
Voltage Recovery Ramp
Time
PwrL V/f Ramp T

The time it takes the output voltage to return to the preset V/f pattern
after speed search (current detection mode) is complete.

0.0 ~ 5.0 s

kVA

Dependent Programming

117

L2-05

0489

Undervoltage Detection
Level
PUV Det Level

Sets the drive's DC Bus undervoltage trip level. If this is set lower than
the factory setting, additional AC input reactance or DC bus reactance
may be necessary.

Voltage

Class

Dependent

Voltage

Class

Dependent

Programming

118

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.