E1-11 Mid Output Frequency B

Setting Range:

0.0 ~ 120.0 Hz

Factory Default: 0.0 Hz

Refer to parameter E1-11 in Appendix A for description details.

E1-12 Mid Output Voltage B

Setting Ranges: 0.0 ~ 255.0 V (240 V Models)

0.0 ~ 510.0 V (480 V Models)

Factory Defaults: 0.0 V (240 V Models)

0.0 V (480 V Models)

Top set up custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be sure that the
following condition is true:

E1-09

≤ E1-07 ≤ E1-06 ≤ E1-11 ≤ E1-04

E1-13 Base Voltage

Setting Ranges: 0.0 ~ 255.0 V (240 V Models)

0.0 ~ 510.0 V (480 V Models)

Factory Defaults: 0.0 V (240 V Models)

0.0 V (480 V Models)

To set up a custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be sure that the
following condition is true:

E1-09

≤ E1-07 ≤ E1-06 ≤ E1-11 ≤ E1-04

Figure 1.38

Figure 38. Custom V/f Pattern Programming Curve

Increasing the voltage in the V/f pattern increases the available motor torque. However, when setting a custom V/f pattern, increase the
voltage gradually while monitoring the motor current, to prevent:

• Drive faults as a result of motor over-excitation
• Motor overheating or excessive vibration

Frequency

E1-09 E1-07

E1-06

E1-04

E1-11

Max Voltage E1-05

Mid Voltage B E1-12

Mid Voltage A E1-08

Base Voltage E1-13

Min Voltage E1-10

Min

Freq

Max

Freq

Base

Freq

Mid

Freq

A

Mid

Freq B

Freq A