P3-02 drive multi / maximum level, If p3-01 = 0: output frequency, If p3-01 = 2: output frequency + feedback level – Yaskawa iQpump Controller Programming Manual User Manual

Page 178

Advertising
background image

178

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.130

Figure 134.

P3-02 Drive Multi / Maximum Level

Setting Range:

0.0 ~ 120.0 Hz

Factory Default: 59.0 Hz

The maximum frequency level used for the multiplex pumping operation (staging) is programmed in the iQpump drive Multi / Maximum
Level (P3-02) is active when the Lead-Lag Control (P3-01) is set to 0 or 2. The multiplex pumping operation (staging) is determined by
the programmed setting of P3-01 as described below.

If P3-01 = 0: Output Frequency

The staging (turning ON) of the auxiliary pump occurs when the output frequency rises above the iQpump drive Multi / Maximum Level
(P3-02) for the time programmed in the Add Pump Delay Time (P3-04). The auxiliary pumps will be added by the control of the multi-
function digital output contact closure (H2-xx = 40 and 41).

If P3-01 = 1: Feedback Level (P3-02: Not Used)

The iQpump drive Multi / Maximum Level (P3-02) is not used when Lead-Lag Control (P3-01) is set to 1.

If P3-01 = 2: Output Frequency + Feedback Level

The staging (turning ON) of the auxiliary pump occurs when the output frequency rises above the iQpump drive Multi / Maximum Level
(P3-02) and the difference between the system’s setpoint minus the feedback level has exceeded the Add Pump Delta Level (P3-03) for
the time programmed in the Add Pump Delay Time (P3-04).

The auxiliary pumps will be added by the control of the multi-function digital output contact closure (H2-xx = 40 and 41).

Refer to Lead-Lag Control (P3-01) for further description of the staging of the pump system.

System

Set-Point

0%

Auto Mode Run

OFF Mode

Multi-function

Output #40

Start System

Start System, Incoming Run Command

TIME

Multi-function

Output #41

PUMP 1 + 2 + 3 RUNNING

Feedback

REMOVE PUMP 3

Open Contact

Shutdown Pump Delay

Time P3-06

Multiplex Stablize Time

P3-11

Multiplex Stablize Time

P3-11

Shutdown Pump Delta Level

P3-05

Shutdown Pump

Delta Level P3-05

REMOVE PUMP 2

Open Contact

Pump 2 & 3

Frequency

Shutdown Level

P3-09, P3-10

Shutdown Pump Delay

Time P3-06

Output Frequency

Advertising