120

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.97

Figure 101. Time Chart for Stall Prevention During Acceleration

The L3-02 parameter is set as a percentage of the iQpump drive rated output current. If the motor capacity is small compared to the
drive’s capacity, or if the motor stalls during acceleration, lower the set value of L3-02.

L3-04 Stall Prevention Selection During Decel

The stall prevention during deceleration function adjusts the deceleration time in order to prevent OV fault trips during deceleration. If
L3-04 = “0: Disabled,” stall prevention is disabled and if the load is large and the deceleration time short enough the iQpump drive may
fault and stop.

If L3-04 = “1: General Purpose,” then the standard stall prevention function is enabled. If, during deceleration, the DC Bus voltage
exceeds the stall prevention level (see

Table 43 on page 120

), the iQpump drive will discontinue decelerating and maintain speed. Once

the DC Bus voltage has dropped below the stall prevention level, the deceleration will continue down to the Speed Command level. See

Figure 102.

.

Table 43 Stall Prevention During Decel

If L3-01 = “2: Intelligent,” the intelligent stall prevention is enabled. The active deceleration time is ignored and the iQpump drive will
attempt to decelerate as quickly as possible without causing the DC Bus voltage to exceed the stall prevention level.

The following

Figure 102.

demonstrates acceleration when L3-04 = “1 General Purpose”.

Figure 1.98

Figure 102. Time Chart for Stall Prevention During Deceleration

Setting

Description

0

Disabled

1

General Purpose (

factory default

)

2

Intelligent

Drive Voltage

Stall Prevention Level during Deceleration (V)

240 Vac

380

480 Vac

E1-01

≥ 400 Vac

760

E1-01 < 400 Vac

660

Output

Frequency

Output

Current

a - Set accel time
b - Accel time is extended

L3-02

t

a

b

t

a

b

TIME

t

a

380/660/760 Vdc

t

Output

Frequency

DC Bus
Voltage

b

a - Set decel time
b - Decel time is extended

TIME