YASKAWA TM.iQp.07 iQpump Controller Programming Manual

239

Table 116 Monitors

Monitor shown only when P1-01 = 3 (MEMOBUS / Modbus Network)

P9-05 Lag Drive Mode

P9-06 Lag Fixed Speed

Setting Range:

0.00 ~ 120.00 Hz

Factory Default: 55.00 Hz

Refer to parameter P9-06 in Appendix A for description details.

P9-07 Lag Fixed Speed Delay

Setting Range:

0.0 ~ 1000 s

Factory Default: 5 s

Refer to parameter P9-07 in Appendix A for description details.

P9-08 Add Pump Mode

P9-09 Add Freq Level

Setting Range:

0.0 ~ 120.0 Hz

Factory Default: 56.0 Hz

Refer to parameter P9-09 in Appendix A for description details.

P9-10 Add Delta Level

Setting Range:

0 ~ 6000.0

Factory Default: 5.0

Refer to parameter P9-10 in Appendix A for description details.

P9-11 Add Delay Time

Setting Range:

0 ~ 3600 s

Factory Default: 10 s

Refer to parameter P9-11 in Appendix A for description details.

Monitor

No.

Addr.

Hex

Monitor Name

Digital Operator Display

Description

U1-68

0009C

Time to Alternate
Time to Alternate

Time remaining before a drive requests alternation which is dependent on P9-04.

Setting

Description

0

Fixed Speed - Runs at the P9-06 setting.

1

PI Regulation - Uses PI to determine speed.

Setting

Description

0

Output Frequency

1

Feedback

2

Feedback + Fout