Yaskawa iQpump Controller Programming Manual User Manual

Page 278

Advertising
background image

278

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

o3-02

0516

Read Allowed Selection
Read Allowable

Enables and disables all digital operator copy functions.
0: Disabled - No digital operator copy functions are allowed.
1: Enabled - Copying allowed

0 ~ 1

0

Programming

139

Pump Basic

P1-01

0600

Pump Mode
Pump Mode

Select type of control operation.
0: Drive Only (Simplex)
1: Drive + 1 Pump
2: Drive + 2 Pumps
3: Memobus network

<0034>

0 ~ 3

0

Programming

141

P1-02

0601

System Units
System Units

0: WC:InchOfWater
1: psi:lb / SqrInch
2: GPM:Gallons / min
3: F:DegFarenheit
4: CFM:Cubic ft / min
5: CMH:Cubic m / hr
6: LPH:Liters / hr
7: LPS:Liters / s
8: Bar:Bar
9: Pa:Pascals
10: C:DegCelsius
11: Ft: Feet

<0032>

12:%: Percent
13: rpm: Revs / min (*su1)

<0034>

14: Hz: Hertz (*su1)

<0034>

0 ~ 14

1

Programming

145

P1-03

0602

Feedback Device Scaling
Fb Dev Scaling

Scaling of feedback device in user units (P1-02=1, e.g. 150 psi).
Digits 1 through 4 set the maximum feedback number. Digit 5
determines the number of decimal places.
Digit 5 = 0: Number format is XXXX
Digit 5 = 1: Number format is XXX.X
Digit 5 = 2: Number format is XX.XX
Digit 5 = 3: Number format is X.XXX
Examples:
01000 = 1000
13000 = 300.0
25000 = 50.00
32000 = 2.000

1 ~ 36000

(system

units

P1-02)

00145

Programming

146

P1-04



0603

Start Level
Start Level

Drive starts when the feedback level drops below the start level for a
time specified in P1-05. This level also specifies the wake up level
when the drive is in Sleep Mode.
If set to a negative value, the feedback level must drop by this amount
below the setpoint.

<0034>

Note:

When PID operates in the reverse mode, the feedback value has

to rise above the start level for the time programmed in P1-05 for the
system to start. A value of 0 disables this function.
If P1-01 = 3, the function is active only on the first drive in the
network.

<0034>

- 999.9 ~

999.9

(system

units

P1-02)

0.0

(system

units

P1-02)

Pump Quick

Setup

147

P1-05



0604

Start Level Delay Time
S-Lvl Delay Time

Drive starts when the feedback level drops below the start level for a
time specified in P1-05.

0 ~ 3600 s

1 s

Programming

148

P1-06



0605

Minimum Pump
Frequency
Min. Pump Freq

Minimum drive frequency when operated in the auto mode.
Programmed value will limit minimum PID output. Minimum value
has to be programmed to a value smaller than P3-09 and P3-10 when
drive is operating in the multiplex mode (P1-01).

0.0 ~

120.0 Hz

40.0 Hz

Pump Quick

Setup

148

P1-07



0606

Low Feedback Level
Low FB Level

The drive will display a “Low Feedback (LFB)” alarm when the
feedback level falls below the programmed level. The alarm will turn
off when the feedback level rises above the programmed Low
Feedback Level plus the Hysteresis Level (P1-13). A value of 0
disables this function. This function is only active during running while
operating in the auto mode.

0.0 ~

6000.0

(system

units

P1-02)

0.0

(system

units

P1-02)

Programming

148

P1-08



0607

Low Feedback Level
Fault Delay Time
Low Lvl Flt Tim

e

The drive will display a “Low Feedback / Water (LFB / LW)” alarm
when the feedback level falls below the programmed level for a time
specified in P1-08. The drive will coast to a stop when a fault occurs. A
value of 0 disables this function. This function is only active during
running while operating in the auto mode.
If P1-01 = 3, the function will stop all drives running on the network
when the system fault occurs.

<0034>

0 ~ 3600 s

5 s

Programming

149



Denotes that parameter can be changed when the drive is running.

(*su1) When P1-02 = 3, parameter P1-03 will have to be set to (120x E1-04 / E2-04) for proper display. When P1-02 = 14, parameter P1-03 will have to be set to the same
value as E1-04 for proper display.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting