YASKAWA TM.iQp.07 iQpump Controller Programming Manual

Parameter List

Table 123 Parameter List

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

Initialization

A1-00



0100

Language Selection
Select Language

Language selection for digital operator display.
0: English
2: Deutsch
3: Francais
4: Italiano
5: Espanol
6: Portugues
*Not returned to factory setting by initialization

0 ~ 6

0

Programming

12

A1-01



0101

Access Level Selection
Access Level

This setting determines which parameters are accessible.
0: Operation Only
2: Advanced Level

0 or 2

2

Programming

12

A1-03

0103

Initialize Parameters
Init Parameters

Used to return all parameters to their factory or user setting.
0: No Initialize
1110: User Initialize (The user must set their own parameter default
values and then parameter o2-03 must be set to “1” to save them. If the
parameter values are changed after o2-03 is set to “1”, the user default
values can be restored by setting A1-03 to 1110.)
2220: 2-Wire Initial
3330: 3-Wire Initial

0 ~ 3330

0

Programming

12

A1-04

0104

Password 1
Enter Password

When the value set into A1-04 does NOT match the value set into A1-
05, parameters A1-01 thru A1-03 cannot be changed. All other
parameters as determined by A1-01 can be changed. Parameter A1-05
can be accessed by pressing the MENU key while holding the RESET
key.

0 ~ 9999

0

Programming

13

A1-05

0105

Password 2
Select Password

0 ~ 9999

0

Programming

13



Denotes that parameter can be changed when the drive is running. * Menu location is Pump Quick Setup when b5-01=1, and Programming when b5-01=0.

Sequence

b1-01

0180

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 ~ 3

0

Programming

14

b1-02

0181

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 Terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN
5: Timed Run

<0034>

0 ~ 3, 5

0

Programming

17

b1-03

0182

Stopping Method
Selection
Stopping Method

Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w / Timer (A new run command is ignored if input before the
time in C1-02 expires.)

0 ~ 3

0

Programming

21

b1-07

0186

Local / Remote Run
Selection
LOC/REM RUN Sel

0: Cycle External RUN - If the run command is closed when switching
from hand (local) mode to auto (remote) mode, the drive will not run.
1: Accept External RUN - If the run command is closed when
switching from hand (local) mode to auto (remote) mode, the drive
WILL run.
Note:

Used with LCD Operator only.

0 ~ 1

0

Programming

b1-08

0187

Run Command Selection
During Program
RUN CMD at PRG

0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus (except when
b1-02 = 0).

0 ~ 1

0

Programming

b1-11

010F

Drive Delay Time Setting
Wait to Run Time

After a run command, drive output will start after this delay time.

0 ~ 600 s

0 s

Programming

24

DC Braking

b2-01

0189

DC Injection Braking
Start Frequency
DCInj Start Freq

Sets the frequency at which DC injection braking starts when ramp to
stop (b1-03 = 0) is selected. If b2-01 < E1-09, DC injection braking
starts at E1-09.

0.0 ~

10.0 Hz

0.5 Hz

Programming