iQpump MEMOBUS / Modbus Status Registers

The data in these registers is not synchronized to any other MEMOBUS / Modbus register, even if read from within the same “read
multiple” MEMOBUS / Modbus Read Command. This data from various iQpump features is copied and scaled for inclusion in the
following register.

MEMOBUS / Modbus Registers

Table 42 MEMOBUS / Modbus Registers

Register Hex

Description

728

Extended Pump Status Word

Bit

Description

0

Sleep Active

1

Start Level Delay

2

Thrust Bearing Active

3

Pre-charge Active

4

High Feedback Detected

5

Low Feedback Detected

6

Transducer Loss

7

Setpoint Not Met

8

Loss of Prime

9

Thermostat Fault

A

Low Flow Detected

B

Utility Delay Active

C

Run / Stop Stopped Condition

D

Run / Stop Finished (cycles complete)

E

Anti-Jam / De-Scale Active

F

Reserved

729

Extended Pump Status Word 1

Bit

Description

0

Sleep Active

1

Start Level Delay

2

Thrust Bearing Active

3

Pre-charge Active

4

High Feedback Detected

5

Low Feedback Detected

6

Transducer Loss

7

Setpoint Not Met

8

Loss of Prime

9

Thermostat Fault

A

Low Flow Detected

B

Utility Delay Active

C

Run / Stop Stopped Condition

D

Run / Stop Finished (Cycles complete)

E

Anti-Jam Active

F

De-Scale Active