154

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Table 63 Parameters

Table 64 Fault

<0034>

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P1-16

87F

Loss of Prime Time
Prime Time Loss

Delay time before a Loss of Prime fault occurs. Pump protection
criteria specified in P1-14 must be met for the drive to fault. On fault
the drive will coast to a stop.

0 ~ 600 s

20 s

Programming

Fault Display

Description

Cause

Countermeasures

LOP

Loss of Prime

Loss of Prime Fault-
Pump has lost its prime.

If the output current drops below the P1-14 Prime Loss Level for
the time specified in P1-16 and the output frequency is at a high
enough level, a “Loss of Prime” fault occurs
Possible causes:

Dry Well, Air in System, No Water

Allow the system to pump water
again (must have resistance in
pump).