Table 125 Fault Trace List

Parameter No.

Addr.

Hex

Fault Trace

U2-01

0080

Current Fault
Current Fault

U2-02

0081

Previous Fault
Last Fault

U2-03

0082

Frequency Reference at Most Recent Fault
Frequency Ref

U2-04

0083

Output Frequency at Most Recent Fault
Output Freq

U2-05

0084

Output Current at Most Recent Fault
Output Current

U2-07

0086

Output Voltage at Most Recent Fault
Output Voltage

U2-08

0087

DC Bus Voltage at Most Recent Fault
DC Bus Voltage

U2-09

0088

Output Power at Most Recent Fault
Output kWatts

U2-11

008A

Input Terminal Status at Most Recent Fault. The format is the same as for U1-10.
Input Term Sts

U2-12

008B

Output Terminal Status at Most Recent Fault. The format is the same as for U1-11.
Output Term Sts

U2-13

008C

Drive Operation Status at Most Recent Fault. The format is the same as for U1-12.
Inverter Status

U2-14

008D

Cumulative Operation Time at Most Recent Fault
Elapsed time

Note:

Fault trace is not executed at CPF00, CPF01, CPF03, UVI and UV2.