B5 pi function, Table 6 pi setpoint options, Yaskawa – Yaskawa iQpump Controller Programming Manual User Manual

Page 32: Tm.iqp.07 iqpump controller programming manual

Advertising
background image

32

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

b5 PI Function

The capability to accept an analog signal as feedback for a PI (Proportional + Integral) control function is built into the drive.

Figure 1.26

Figure 26. PI Block Diagram

The analog feedback to the iQpump drive for the PI control is via the A2 terminal. The iQpump drive must be programmed (H3-09 = “B:
PI Feedback”) to use terminal A2 as feedback for the PI functionality of the drive.

The PI Setpoint can be configured to come from one of many different inputs or parameters.

Table 6 on page 32

describes the options for

originating the PI Setpoint.

Table 6 PI Setpoint Options

In some situations there are two feedback inputs. The drive can be programmed to maintain a set differential between two analog signals.
If input A2 is configured as a “PI Differential Mode” (H3-09 = “16: PI Differential”), then the iQpump drive will maintain a set
difference between the measurements read on inputs A1 and A2. This differential setpoint is programmed by parameter (b5-07).

The PI Setpoint will be read from:

If these conditions are true

Status of b5-18 =

Status of MEMOBUS /

Modbus Register 0Fh bit 1

Status of b1-01 =

Parameter b5-19

1

N/A

N/A

MEMOBUS/Modbus Register 06H

0

ON

N/A

D1-01

0

OFF

0

Terminal A1

0

OFF

1

Serial Comm.

0

OFF

2

Option PCB

0

OFF

3

Option Card

Serial Com

Terminal A1

D1-01

D1-04

D1-02

Output

frequency

P

1/t

1/t

Z

-1

b1-01

1

2

3

Frequency Reference

using multi-step

command

Frequency reference

(U1-01)

PI Set Point

(U1-38)

Proportional

gain

b5-02

I-time
b5-03

I - limit

b5-04

PI Limit

b5-06

PI delay time

b5-08

PI offset

(b5-07)

+

+

+ +

PI output monitor

(U1-37)

b5-01=0

ON

PI control is OFF under the following
conditions:
- b5-01=0
- H3-xx=19 and the terminal status is
ON

Upper limit
Fmax x109%

+

+

b5-01=3

b5-01=1

Lower limit 0

4

Integral Hold

H1-xx=31

Integral Reset

H1-xx=30

PI Output

Characteristic

b5-09

1

0

PI SFS

b5-17

PI SFS cancel

H1-xx=34

0

1

P1-03

Scaling

Terminal A1

Terminal A2

PI Differential

Fdbk. H3-09=16

1

0

H3-09=B

1

0

1

0

PI Differential

Fdbk. H3-09=16

PI Differential

Fdbk. H3-09=16

Z

-1

1

0

1

0

PI Input

Caracteristic

H1-xx=35

1

0

Z

-1

PI SFS

b5-17

PI SFS cancel

H1-xx=34

0

1

Scaling

PI Input
(U1-36)

+

-

0

1

PI Differential

Fdbk. H3-09=16

PI Feedback

(U1-24)

Scaling

1

0

1

0

b5-07

0

1

+

+

PI Differential
Fdbk. H3-09=16

-

+

+

+

b5-10

PI Output

Gain

PI offset

H3-09=16

SFS

OFF

PI Differential
Fdbk. H3-09=16

Characteristic

H1

P1-06
Minimum
Pump Speed

Speed Command / PI Setpoint

PI Setpoint

PI Feedback

Advertising